Plan Review Notes
Plan Review Notes For Permit 02021905
Permit Number 02021905
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-02 00:00:00PLUMBING PLAN REVIEW, DENIED FBC-2001
 COMPLY WITH THEFOLLING.
 (1) SEC 424.2.6 ENGINEERING DESIGN,SHOW
 ON PLANS, PER FBC- 2001
 (2) SEC 424.2.7.2 SHOW A DETAIL OF MOUNT
 ING AND AHCHORING POOL EQUIPMENT.
 (3) SEC 424.2.9 AND LOCAL ORD #2853-95
 BACK FLOW PREVENTER REQUIRED ON WATER
 SERVICE,
 (4)SEC 424.2.13.2 PURPLE PRIMER REQUIRED
 ON PVC PIPING, FBC-2001 PLUMBING.
 (5) 424.2.14.1 THRU 424.2.14.5 POOL,SPA
 WATER HEATING EQUIPMENT.
 (6) 424.2.15 SEPERATE PLANS AND PERMIT
 REQUIRED FOR GAS FIRED POOL HEATER.
 END OF COMMENTSPAUL SCHMITZ