| Plan Review Notes For Permit 02021905 |
| Permit Number |
02021905 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-02 00:00:00 | PLUMBING PLAN REVIEW, DENIED FBC-2001 | | | COMPLY WITH THEFOLLING. | | | (1) SEC 424.2.6 ENGINEERING DESIGN,SHOW | | | ON PLANS, PER FBC- 2001 | | | (2) SEC 424.2.7.2 SHOW A DETAIL OF MOUNT | | | ING AND AHCHORING POOL EQUIPMENT. | | | (3) SEC 424.2.9 AND LOCAL ORD #2853-95 | | | BACK FLOW PREVENTER REQUIRED ON WATER | | | SERVICE, | | | (4)SEC 424.2.13.2 PURPLE PRIMER REQUIRED | | | ON PVC PIPING, FBC-2001 PLUMBING. | | | (5) 424.2.14.1 THRU 424.2.14.5 POOL,SPA | | | WATER HEATING EQUIPMENT. | | | (6) 424.2.15 SEPERATE PLANS AND PERMIT | | | REQUIRED FOR GAS FIRED POOL HEATER. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|