| 2002-04-10 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 02021900 |
| | 8521 EGRET LAKES LANE |
| | CONT: CLASSIC DESIGNER HOMES, INC |
| | TEL: (954) 345-2727 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS STANDARD BUILDING CODE |
| | |
| | 1)- FL ENERGY CODE 601. MISSING ENERGY |
| | CALS W/ MANUAL J |
| | 2)- SBC 1804.2.7.2(3) SOILS REPORT/ W |
| | MINIMUM BEARING VALUE. |
| | 3)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | A) GARAGE DOORS INDICATE (CIRCLE OR |
| | HIGHLIGHT) WHICH DOOR SHALL BE USED. |
| | B) THE VARIOUS REPORTS SUBMITTED INDI- |
| | CATE THE USE OF IMPACT RESISTANT GLAZING |
| | AND THER REPORTS NON IMPACT GLAZING, |
| | THERE IS NO INFORMATION AS TO STORM |
| | SHUTTERS, OR A KEY INSTALATION PLAN NOR |
| | A INSTALLTION SCHEDULE. |
| | 4)- TRUSS ANCHOR SCHEDULE, MARK TC-5 |
| | INDICATES A ALLOWABLE UPLIFT OF 2233 |
| | FOR A DOUBLE STRAP, THE USP CATALOG ONLY |
| | ALLOWS 2090 LBS UPLIFT. |
| | 5) TRUSS ANCHOR SCHEDULE, MARK TC-7 |
| | INDICATES AN UPLIFT OF 1433, THE CATALOG |
| | INDICATES 1350 FOR 1 1/2" #10 NAILS, |
| | 1520 FOR #10'S CLICHED OVER, WHAT VALUE |
| | IS TAKEN FOR 1433? |
| | 6) SHEET A-6 TRUSS LAYOUT: |
| | A) 2M GIRDER OVER THE SITTING RM 2200 |
| | VALUE TO HIGH FOR TYPE ANCHOR VALUED @ |
| | 2090. |
| | B) GIRDER OVER THE DINING RM. A) 4495LB |
| | DETAIL17/A-9 UPLIFT VALUE TO HIGH, PLUS |
| | NO FI/F2 VALUE.SAME GIRDER TRUSS, INDICA |
| | TES 13,747 SAME DETAIL WHEN THERE IS A |
| | COLUMN INDICATED BELOW? |
| | C) COVERED PATIO A) INDICATES 1986 LBS |
| | UPLIFT, 2 STRAPS VS SHEET A-6 INDICATING |
| | A BUCKET? B) SAME DETAIL, SIDE ELEVATION |
| | CONNECTION WITH 3396 LBS UPLIFT NO INFOR |
| | MATION GIVEN, BUCKET? |
| | D) DETAIL 18/A9 INDICATES 3 SIMPON FACE |
| | MOUNTED BUCKETS, AT THE CORNER OF A |
| | COLUMN, WITH ONE OF THE FLANGES BENT. |
| | THIS DETAIL IS FOR SIMPSON BUCKETS, |
| | SIMPSON VOIDS ANY WARRENTY ON THERE |
| | PRODUCTS,SEE TERMS & CONDITIONS OF SALE |
| | & WARRANTY. THE SECOND ISSUE IS THE FLAN |
| | GE IS ONLY 2" WIDE, WHAT FACTOR IS TO BE |
| | USED IN DERATING BECAUSE OF THE EDGE |
| | DISTANCE? |
| | E) FAMILY ROOM GIRDER @ SLIDING GLASS |
| | DOORS, 5510 LBS UPLIFT, NO CONNECTION TO |
| | BEAM? |
| | 7) CONTRACTOR TO SUBMIT PLANS TO |
| | P B COUNTY FOR COUNTY IMPACT FEE ASSESS- |
| | MENT. |
| | 8) CITY ADDITIONAL FEE DUE. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |