Plan Review Notes
Plan Review Notes For Permit 02021896
Permit Number 02021896
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-05 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) PLEASE ROUTE PLANS TO DEPT. OF BUSIN-
 ESS REGULATION HOTEL & BUSINESS DIVISION
 FOR PLAN REVIEW BEFORE RESUBMITTING FOR
 PLAN REVIEW FOR PERMIT.
 2) SHT SM.P1 PLUMBING & RISER PLANS, ICE
 BIN TO BE INDIRECT WASTE TO FLOOR SINK.
 SPC SEC 804.5/804.5.1.
 3) SHT SM.P1 PLUMBING & RISER PLANS, 3
 COMPARTMENT SINK TO BE INDIRECT WASTE TO
 FLOOR SINK.
 4) SHT SM.P1 SINK SUMP TO BE LOCATED
 BELOW SLAB TO TAKE INDIRECT WASTE FROM
 FLOOR SINK.
 5) SHT SM.P1 VENT FROM SUMP SHALL VENT
 SEPARATELY. SEC 915
 6) SHT SM.P1 DRAINAGE FROM SUMP SHALL
 NOT DRAIN INTO MOP SINK. AN APPROVED
 INDIRECT WASTE RECEPTOR SHALL BE USED.
 (FLOOR SINK).
  
 REVEIW BY KEN STEVENS
 (561)659-8096 EXT 8377