| 2002-03-06 00:00:00 | |
| | NO MECHANICAL PLANS SUBMITTED FOR |
| | REVIEW.PLEASE PROVIDE PLANS WITH |
| | MECHANICAL PERMIT APPLICATION. |
| | |
| | PLEASE NOTE, BATHROOM SHALL HAVE A |
| | WINDOW WITH A MINIMUM OF 3 SQ FT OF |
| | OPEN SPACE OR AIR SHALL BE MECHANICALLY |
| | EXHAUSTED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |
| | |
| | MECHANICAL PERMIT 00120524 |
| | |
| | PLEASE PROVIDE MANUFACTURER SUBMITTAL |
| | DATA FOR DRYERS BEING INSTALLED IN |
| | UNITS THAT THE IN-LINE FAN HAS BEEN |
| | DELETED. EXHAUST DUCT EXCEEDS 25FT |
| | MAXIMUM AS PER 1997 SMC 509.3. |
| | |
| | REVISIONS APPROVED WITH THE EXCEPTION |
| | OF"PROPOSED KITCHEN HOOD".TERMINATION |
| | FOR GREASE DUCT SHALL COMPLY WITH NFPA |
| | 96 AND 1997 SMC CHAPTER 5.PLEASE NOTE |
| | AS PER 1997 SMC 506.1, TERMINATION OF |
| | EXHAUST SHALL BE LOCATED 10 FT FROM ANY |
| | ADJACENT BUILDING, PARKING AREA, |
| | ADJACENT PROPERTY LINE, WINDOW, DOOR OR |
| | AIR INTAKE.ADDITIONAL PLANS & PERMITS |
| | REQUIRED FOR HOOD (GREASE DUCT & MAKEUP |
| | AIR), FIRE SUPRESSION, AND WALK-IN |
| | COOLERS/FREEZERS.PROVIDE MANUFACTURER |
| | SUBMITTAL DATA WITH PLANS & PERMIT |
| | APPLICATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |