| Plan Review Notes For Permit 02021837 |
| Permit Number |
02021837 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-26 00:00:00 | A) BUILDING ADDRESS REQUIRED. | | | B) WRONG LIFE SAFETY CODE REFERENCED | | | ON PLANS. SHOULD READ THE FLORIDA | | | FIRE PREVENTION CODE, 2000 EDITION OF | | | THE LIFE SAFETY CODE. | | | C) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | D) STORAGE ROOM 117,AND | | | STORAGE/MECHANICAL ROOM 104 ARE TO BE | | | AT LEAST ONE HOUR FIRE RATED AND BE | | | EQUIPPED WITH AT LEAST C LABELED FIRE | | | DOORS, SINCE NO FIRE SPRINKLERS ARE | | | PLANNED. | | | E) DOOR 122 FOR THE JANITOR'S ROOM | | | IS NOT FIRE RATED LIKE THE ROOM IS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|