| 2002-04-29 00:00:00 | CHECKLIST: |
| | 1-BRING DRAWINGS TO PALM BEACH COUNTY TO |
| | PAY IMPACT FEES. BRING BACK STAMPED |
| | DRAWINGS AND PAID RECEIPT. |
| | 2-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS AND SEC. 2405.2 SBC 1997. |
| | 3-REVISE ROOF SLOPE. MIN. SLOPE TO BE |
| | 1/4" PER FT. SEC. 1503.1.2.3 SBC 1997. |
| | 4-ENGINEER TO SPECIFY ON PLANS HOW IS |
| | NEW FOUNDATION AND WALL GOING TO BE |
| | ATTACHED TO EXISTING FOUNDATION AND |
| | WALLS. SEC. 104.2.2 CITY AMENDMENTS TO |
| | SBC 1997. |
| | 5-PROVIDE COMPLETE WALL SECTION/DETAIL |
| | THRU EXISTING WALL AND NEW ROOF. |
| | SPECIFY HOW NEW 4X6 ROOF JOISTS ARE |
| | GOING TO BE ANCHORED USING SIMPSON OR |
| | USP CONNECTOR SPECIFIED ON ROOF |
| | FRAMING PLAN. NOTE: THIS CONNECTOR IS |
| | DESIGNED TO BE EMBEDDED INTO CONCRETE. |
| | HOW IS THE CONNECTOR GOING TO BE |
| | EMBEDDED INTO EXISTING CONCRETE BEAM? |
| | 6-CLARIFY WHICH TYPE OF CONCRETE SLAB IS |
| | GOING TO BE USED. WALL SECTION CALLS |
| | FOR WIRE MESH WHILE FOUNDATION PLAN |
| | CALLS FOR FIBER MESH. |
| | 7-PROVIDE PRODUCT APPROVAL FOR: |
| | A)FLAT ROOF SYSTEM SPECIFIED ON PLANS. |
| | B)SINGLE HUNG WINDOWS WINDOWSWITH |
| | APPROVED DRAWINGS. |
| | C)EXTERIOR DOOR WITH APPROVED DRAWINGS. |
| | D)STORM SHUTTERS WITH APPROVED DRAWINGS. |
| | SPECIFY SYSTEM AND ANCHOR TYPE AND |
| | SPACING TO BE USED. |
| | 8-OWES $83.04 FOR UPDATED VALUATION AND |
| | RADON FEES. |
| | 9-ENGINEER SPECIFY THE DESIGN PRESSURES |
| | CALCULATED FOR EXTERIOR OPENINGS PER |
| | SECTION 1606 SBC 1997. |