| 2002-03-13 00:00:00 | ******************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE NOTE LOAD CALCULATIONS/ |
| | PANEL SCHEDULE ONLY SHOW NEW ELECTRICAL |
| | LOAD/LAYOUT? PLEASE INCLUDE ALL EXISTING |
| | LOADS. WASHER, DRYER,A/C, ETC |
| | CLARIFY IF THE NEW A/C SYSTEM IS GOING |
| | TO FEED EXSITING HOUSE ALSO, OR IS THERE |
| | ANOTHER SYSTEM? |
| | |
| | 2)NOTE: PLEASE NOTE SD REQ`D OUTSIDE |
| | BEDROOM. NFPA-72 2-2.1.1.1.PLEASE NOTE |
| | SD, NOT IN KITCHEN. NFPA-2-5.2.1.6. |
| | 3)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | A/C COND UNIT. 309.2 MECH CODE. |
| | |
| | 4)NOTE: PLEASE NOTE THAT SOME LOADS |
| | SHOWN ON PANEL SCHEDULE EXCEED RATINGS |
| | OF BRKRS AND ALSO MAX OF 80% OF BRKR. |
| | 3KW ON 15A, 2KW ON 15A. PLEASE CORRELATE |
| | OCP WITH LOADS AND WIRE SIZES. |
| | |
| | 5)NOTE: PLEASE VERFIY IF 200A PANEL |
| | SHOWN IS NEW. PLEASE ALSO NOTE THAT |
| | PANEL IS SHOWN WITH A MAIN CIRCUIT BRKR. |
| | PLEASE NOTE WITH A MAIN DISC ON THE |
| | LINE SIDE, A MCB IS NOT REQ`D. |
| | PLEASE CLARIFY. IF PLANS SHOW, THEN ONE |
| | WILL BE REQ`D TO BE INSTALLED. |
| | PLEASE SUBMIT AIC RATINGS FOR ANY NEW |
| | EQUIPMENT BEING INSTALLED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |