Plan Review Notes
Plan Review Notes For Permit 02021790
Permit Number 02021790
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-13 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS/
 PANEL SCHEDULE ONLY SHOW NEW ELECTRICAL
 LOAD/LAYOUT? PLEASE INCLUDE ALL EXISTING
 LOADS. WASHER, DRYER,A/C, ETC
 CLARIFY IF THE NEW A/C SYSTEM IS GOING
 TO FEED EXSITING HOUSE ALSO, OR IS THERE
 ANOTHER SYSTEM?
  
 2)NOTE: PLEASE NOTE SD REQ`D OUTSIDE
 BEDROOM. NFPA-72 2-2.1.1.1.PLEASE NOTE
 SD, NOT IN KITCHEN. NFPA-2-5.2.1.6.
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C COND UNIT. 309.2 MECH CODE.
  
 4)NOTE: PLEASE NOTE THAT SOME LOADS
 SHOWN ON PANEL SCHEDULE EXCEED RATINGS
 OF BRKRS AND ALSO MAX OF 80% OF BRKR.
 3KW ON 15A, 2KW ON 15A. PLEASE CORRELATE
 OCP WITH LOADS AND WIRE SIZES.
  
 5)NOTE: PLEASE VERFIY IF 200A PANEL
 SHOWN IS NEW. PLEASE ALSO NOTE THAT
 PANEL IS SHOWN WITH A MAIN CIRCUIT BRKR.
 PLEASE NOTE WITH A MAIN DISC ON THE
 LINE SIDE, A MCB IS NOT REQ`D.
 PLEASE CLARIFY. IF PLANS SHOW, THEN ONE
 WILL BE REQ`D TO BE INSTALLED.
 PLEASE SUBMIT AIC RATINGS FOR ANY NEW
 EQUIPMENT BEING INSTALLED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372