| 2002-03-13 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 02021697 |
| | 1219 FLORIDA AV |
| | CONT: KEITH TURNEY |
| | TEL: 684-0905 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | FLBC= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)- PLANS SUBMITTED BETWEEN JAN.1, 2002 |
| | AND FEB. 28, 2002 SHALL INDICATE AS TO |
| | WHICH CODE THEY ARE DESIGNED TOO? THIS |
| | REVIEW SHALL BE COMPLETED UNDER THE |
| | 1997 SBC. |
| | |
| | 2) PLANS INDICATE A WINDOW DRAWN IN ON |
| | THE EAST SIDE, NOT AS PART OF THE ARCH. |
| | ORIGINAL DEPICTION, ARCH. TO REVIEW AND |
| | OK BY LETTER FORM SIGN & SEAL. TO BE APP |
| | ROVED BY HISTORICS BEFORE PLANS ARE ISSU |
| | ED. |
| | |
| | 3)- THE PLANS DO NOT INDICATE DESIGN |
| | PARAMETERS & ASSUMPTIONS AS REQUIRED |
| | BY CHAPTER 16, FL. ST. S 481 & 553. |
| | |
| | 4)- THE PLANS & PERMIT APPLICATION IN- |
| | DICATE THAT THE NORTH & WEST WALLS ARE |
| | TO REPLACED AS WELL AS THE CONCRETE SLAB |
| | SBC 1804.1.3 THE BOTTOM OF THE FOOTER |
| | SHALL BE 12" BELOW GRADE. THE SUB-SHEATH |
| | ING REQUIRES A CLEARENCE OF 6" BETWEEN |
| | THE EARTH AND SHEATHING UNLESS SHEATHING |
| | AND FRAMING ARE OF APPROVED PRESERVATIVE |
| | TREATED WOOD OR APPROVED NATURALLY |
| | DURABLE WOOD. |
| | |
| | 5)- SBC 1606.2.5.2 THE PRESSURE ZONES |
| | ARE TO BE INDENTIFIED ON THE PLANS, POSI |
| | TIVE & NEGITIVE PRESSURES FOR ALL OPEN- |
| | INGS. |
| | |
| | 6)- THE PRODUCT APPROVAL SUBMITTAL FORM |
| | FOR THE GARAGE DOOR IS TO BE REJECTED |
| | WITHOUT CALCULATIONS INDICATING THAT |
| | THE DOOR AND HARDWARE MEET THE WIND |
| | REQUIREMENTS OF CHAPTTER 16. |
| | |
| | 7)- SBC TABLE 600 FOR TYPE VI STRUCTURES |
| | LESS THAN 3'-0" FROM THE PROPERTY LINE |
| | A 1 HR RATING IS REQUIRED FOR THE EXTER- |
| | IOR WALL, INDICATE CODE COMPLIANCE |
| | SBC 709.6.2.2. |
| | |
| | 8)- SBC 1007.3.1 TREADS & RISERS 2R+1T= |
| | 24TO 25". |
| | |
| | 9)- SBC 1203.4.2 EVERY TOLIET ROOM SHALL |
| | HAVE A WINDOW OR MECHANICAL VENTILATION. |
| | |
| | 10)- PLANS DO NOT INDICATE ANY HURRI- |
| | CANE STRAPPING FROM RAFTER TO RAFTER |
| | AT THE RIDGE. |
| | |
| | 11)- PRODUCT TESTING REPORTS, THE STEEL |
| | SIDE DOOR REPORT EXPIRED, MISSING REPORT |
| | FOR ROOFING MATERIALS. |
| | |
| | 12)- CONTRACTOR TO SSUBMIT PLANS TO THE |
| | COUNTY FOR IMPACT FEE ASSESSMENT. |
| | |
| | 13)- THE PERMIT VALUE OF $19,000.00 IS |
| | LOW. THE AVERAGE FOR TYPE VI CONST IS |
| | 49.92 X 900= 45,000 WITHOUT VALUE TO |
| | THE 900 SQ FT TO THE FIRST FLOOR. |
| | |
| | 14)- HOLD ON PROPERTY, 4X FEE BLDG W/O |
| | FENCE PERMIT, 01/24/01 BOB COMPTON. |
| | |
| | 15)- TO PAY ADDTIONAL RADON FEES. |