Plan Review Notes
Plan Review Notes For Permit 02021651
Permit Number 02021651
Review Stop B
Sequence Number 1
Notes
Date Text
2002-03-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2.2SHEET D-1, DEMOLITION
 PLAN.STATE THE TYPE OF CONSTRUCTION OF
 THE EXISTING WALLS WHICH ARE TO BE
 DEMOLISHED.ARE THEY LOADBEARING?
  
 3) SBC TABLE 704.2.4FOR GROUP R1
 (HOTEL/MOTEL) OCCUPANCY, EXIT ACCESS
 CORRIDORS SHALL HAVE A FIRE RESISTANCE
 RATING OF 1 HOUR IF NON-SPRINKLERED OR
 1/2 HOUR IF SPRINKLERED.THE PROPOSAL
 IS FOR REPLACEMENT OF THE EXISTING
 CORRIDOR WALLS WITH 3 FEET HIGH
 PARTITIONS.REINSTATE THE CORRIDORS OR
 SUBMIT LIFE SAFETY PLANS TO SHOW ALL
 AREAS WITH MEANS OF EGRESS VIA THESE
 CORRIDORS.
 ***FOLLOW-UP:
 LIFE SAFETY PLAN REVIEWED ON 3/21/02.
 EITHER ENCLOSE THE PROPOSED DINING WITH
 1/2 HOUR FIRE RATED WALLS/GLAZING AND
 FIRE DOORS OR LEAVE PROPOSED DINING OPEN
 AND INSTALL SMOKE CONTROL FIRE DOORS
 ACROSS THE CORRIDOR IN TWO LOCATIONS AS
 MARKED ON THE ATTACHED PLAN.THE DOORS
 SHALL BE DOUBLE DOORS WITH PAIRED LEAFS
 OPENING IN OPPOSITE DIRECTIONS.THE
 DOORS SHALL NORMALLY BE HELD OPEN BY
 DEVICES CONNECTED TO THE FIRE ALARM SUCH
 THAT THEY CLOSE UPON A FIRE ALARM
 ORIGINATING FROM ANYWHERE IN THE
 BUILDING.THERE SHALL BE A SMOKE
 DETECTOR ON EACH SIDE OF BOTH DOORSETS
 (4 HEADS IN TOTAL) AND ADDITIONAL EXIT
 SIGNAGE SHALL BE INSTALLED TO DIRECT
 OCCUPANTS TO EXITS BEYOND THE DOORS,
 AFTER THEY HAVE CLOSED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499