| 2002-03-14 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SBC* 104.2.2SHEET D-1, DEMOLITION |
| | PLAN.STATE THE TYPE OF CONSTRUCTION OF |
| | THE EXISTING WALLS WHICH ARE TO BE |
| | DEMOLISHED.ARE THEY LOADBEARING? |
| | |
| | 3) SBC TABLE 704.2.4FOR GROUP R1 |
| | (HOTEL/MOTEL) OCCUPANCY, EXIT ACCESS |
| | CORRIDORS SHALL HAVE A FIRE RESISTANCE |
| | RATING OF 1 HOUR IF NON-SPRINKLERED OR |
| | 1/2 HOUR IF SPRINKLERED.THE PROPOSAL |
| | IS FOR REPLACEMENT OF THE EXISTING |
| | CORRIDOR WALLS WITH 3 FEET HIGH |
| | PARTITIONS.REINSTATE THE CORRIDORS OR |
| | SUBMIT LIFE SAFETY PLANS TO SHOW ALL |
| | AREAS WITH MEANS OF EGRESS VIA THESE |
| | CORRIDORS. |
| | ***FOLLOW-UP: |
| | LIFE SAFETY PLAN REVIEWED ON 3/21/02. |
| | EITHER ENCLOSE THE PROPOSED DINING WITH |
| | 1/2 HOUR FIRE RATED WALLS/GLAZING AND |
| | FIRE DOORS OR LEAVE PROPOSED DINING OPEN |
| | AND INSTALL SMOKE CONTROL FIRE DOORS |
| | ACROSS THE CORRIDOR IN TWO LOCATIONS AS |
| | MARKED ON THE ATTACHED PLAN.THE DOORS |
| | SHALL BE DOUBLE DOORS WITH PAIRED LEAFS |
| | OPENING IN OPPOSITE DIRECTIONS.THE |
| | DOORS SHALL NORMALLY BE HELD OPEN BY |
| | DEVICES CONNECTED TO THE FIRE ALARM SUCH |
| | THAT THEY CLOSE UPON A FIRE ALARM |
| | ORIGINATING FROM ANYWHERE IN THE |
| | BUILDING.THERE SHALL BE A SMOKE |
| | DETECTOR ON EACH SIDE OF BOTH DOORSETS |
| | (4 HEADS IN TOTAL) AND ADDITIONAL EXIT |
| | SIGNAGE SHALL BE INSTALLED TO DIRECT |
| | OCCUPANTS TO EXITS BEYOND THE DOORS, |
| | AFTER THEY HAVE CLOSED. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |