Plan Review Notes
Plan Review Notes For Permit 02021641
Permit Number 02021641
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-12 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT A-4 ROOF PLAN "A" - SUBMIT ROOF
 DRAIN CALCULATIONS FOR NEW ROOF AREAS.
 SHOW DETAILS FOR SECONDARY DRAINS FOR
 NEW TERRACE ROOF, NEW ROOF INTERIOR ADD.
 NEW CURVED BALCONY ROOF.
 2) SHT A-4 ROOF PLAN "A" - "REMOVE AND
 PATCH EXIST. SCUPPERS @ PERIMETER WALL",
 EXPLAIN HOW SCUPPERS CAN BE REMOVED AND
 PATCHED WHEN THEY ARE THE SECONDARY
 DRAINS FOR THIS ROOF.
 3) SHT A-4 ROOF PLAN "A" - PLEASE PRO-
 VIDE ROOF DRAIN CALCULATIONS FOR EXIST.
 ROOF. ADD AREAS OF NEW ROOFS BEING ADDED
 TO AREA OF ROOF. (ROOFS ADDED - STAIR
 TOWERS #'S 1 & 3, SERVICE AND PASSENGER
 ELEVATORS, AND ROOF WEST OF SERV. ELEV.)
 SHOW DETAILS FOR ALL SECONDARY DRAINS.
 GIVE LOCATIONS ON ROOF PLAN FOR PRIMARY
 AND SECONDARY DRAINS EXISTING.
 4) SHT A-4 ROOF PLAN "A" - PLEASE SHOW
 DETAILS FOR REACTIVATING SCUPPERS AS RE-
 FERED TO IN NOTE. (ALSO NOTED ON SHT P-6
 5) SHT A-5 ROOF PLAN "B" - PLEASE SUBMIT
 CALCULATIONS FOR EXISTING ROOF DRAIN.
 SHOW PRIMARY AND SECONDARY DRAIN LOCAT-
 IONS. GIVE SQ FOOT AREAS FOR EACH DRAIN
 AND DRAIN SIZE.
 6) SHT A-5 ROOF PLAN "B" - PLEASE SUBMIT
 DETAILS ON HOW THE SECONDARY ROOF DRAINS
 (SCUPPERS) CAN BE REMOVED AND PATCHED,
 AND ONE OVERSIZED SECONDARY DRAIN WILL
 WORK ON A FLAT ROOF.
 7) PLEASE SUBMIT A STORM RISER DIAGRAM
 FOR ALL NEW ROOFS. SHOW AREA FOR EACH
 DRAIN, PIPE SIZE, PITCH FOR PIPE, AND
 SHOW ACCUMULATION OF SQUARE FOOTAGE FOR
 PIPE AS EACH DRAIN IS ADDED. SHT P-6
 SHOWS EXISTING ROOF DRAIN BEING REMOVED.
 8) SHT A-4 STAIRWAY #3, PLEASE SUBMIT
 DETAILS FOR FLUE EXTENTION. INDICATE
 WHAT FIXTURE THE FLUE IS VENTING. SUBMIT
 A DETAIL SHOWING SIZE, LENGTH OF FLUE &
 GIVE TOTAL BTU'S OF FIXTURE.
 9) SHT ID.2 HDCP STALLS IN ROOMS 110 &
 111 DO NOT MEET FACBC-97 CODE. LAV REQD.
 IN HDCP STALLS. SEC 4.1.7.3 FIG 30(E).
 10) SHT ID.11 FOUNTAIN. PLEASE SUBMIT
 PLUMBING DETAIL FOR FOUNTAIN. SHOW PIP-
 ING, BACKFLOW FOR WATER SERVICE, PUMPING
 FILTER ECT. SEPARATE PERMITS REQUIRED
 FOR FOUNTAIN.
 11) SHT P-1 GENERAL NOTES #16 AIR CHAMB-
 ERS. AIR CHAMBERS ARE A QUICK FIX AND
 REQUIRED AN ACCESS PANEL AND SHALL BE RE
 CHARGABLE. APPROVED WATER HAMMER ARREST-
 ORS DO NOT REQUIRE ACCESS PANELS.
 12) SHT P-1 PLUMBING SPECIFICATIONS #1
 CODE IN EFFECT IS SPC-94 NOT SOUTH FLA
 BLDG CODE.
 13) SHT P-1 PLUMBING SPECIFICATIONS #19-
 (C) DIELECTRIC UNIONS NOT APPROVED FOR
 WATER USAGE. GAS FITTING ONLY.
 14) SHT P-2 PART DOMESTIC WATER PUBLIC
 TOILETS RISER DIAGRAM. SEE PLAN REVIEW
 NOTE #11 AIR CHAMBERS. 1/2" TRAP PRIMERS
 ARE FEEDING WATER CLOSETS NOT TRAP PRIM-
 ERS.
 15) SHT P-2 SANITARY RISER DIAGRAM,
 1-1/2" TO URNAL NOT APPROVED. MINIMUM 2"
 WASTE TO URNAL. SPC TABLE 713.2
 16) SHT P-2 SANT. RISER DIAGRAM, FLOOR
 DRAINS NOT VENTED PROPERLY.
 17) SHT P-3 COMBINATION WASTE AND VENT
 SYSTEM FOR FLOOR SINKS REQUIRED ONE VENT
 BEFORE FIRST FIXTURE. SPC SEC 921.4.2
 18) SHT P-3 POND, INDIRECT WASTE FROM
 POND SHALL NOT DRAIN INTO MOP SINK AS
 INDICATED. POND SHALL DRAIN INTO AN IN-
 DIRECT WASTE RECEPTOR THAT IS APPROVED.
 (FLOOR SINK)SHOW DETAILS.
 19) SHT P-3 POND, BACKFLOW IS REQUIRED
 FOR WATER SUPPLY TO POND. PLEASE PROVIDE
 DETAIL.
 20) SHT P-8 SEE REVIEW COMMENTS #14 - 15
 -&-16. THESE COMMENTS APPLY TO SHT P-8
 AS WELL AS RISER DIAGRAMS ON SHT P-8.
 PLEASE SHOW DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377