Plan Review Notes
Plan Review Notes For Permit 02021641
Permit Number 02021641
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-02-27 00:00:00A) NO FIRE HYDRANT LOCATIONS IDENTIFIED
 ON SITE PLAN.
 B) PANIC HARDWARE REQUIRED ON EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS.
 C) PLEASE INDICATE USE OF TERRACE.
 D) PLEASE INDICATE LOCATIONS OF FIRE
 ALARM EQUIPMENT IN NEW AREAS.
 E) IT WAS NOTED THAT EXITING FROM A
 BALLROOM ENTERS A RECEIVING ROOM. EXIT
 ACCESS IS NOT PERMITTED THROUGH STORAGE
 ROOMS.
 F) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 G) PLEASE PROVIDE A FURNITURE PLAN FOR
 NEW ROOMS OR AREAS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910