| Plan Review Notes For Permit 02021641 |
| Permit Number |
02021641 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-27 00:00:00 | A) NO FIRE HYDRANT LOCATIONS IDENTIFIED | | | ON SITE PLAN. | | | B) PANIC HARDWARE REQUIRED ON EXIT | | | DOORS SUBJECT TO AN OCCUPANCY OF 100 | | | OR MORE PERSONS. | | | C) PLEASE INDICATE USE OF TERRACE. | | | D) PLEASE INDICATE LOCATIONS OF FIRE | | | ALARM EQUIPMENT IN NEW AREAS. | | | E) IT WAS NOTED THAT EXITING FROM A | | | BALLROOM ENTERS A RECEIVING ROOM. EXIT | | | ACCESS IS NOT PERMITTED THROUGH STORAGE | | | ROOMS. | | | F) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | G) PLEASE PROVIDE A FURNITURE PLAN FOR | | | NEW ROOMS OR AREAS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|