| 2002-03-13 00:00:00 | *************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE E-9 NEEDS TO SHOW |
| | CIRCUITING AND TO WHAT PANELS THESE |
| | FIXTURES WILL BE GOING TO? |
| | VOLTAGE/ LOADING OF CIRCUITS. |
| | |
| | 2)NOTE: PLEASE SEE ANY FIRE REVIEW |
| | COMMENTS THAT MAY AFFECT ELECTRICAL |
| | PLANS FOR EXIT LIGHTING. |
| | |
| | 3)NOTE: PLEASE NOTE THAT NOT ENOUGH |
| | INFORMATION IS PROVIDED FOR "PART PLAN |
| | RISER" SHOWN ON E-3. |
| | PLEASE NOTE THAT NOTE FOR TAPPING |
| | MENTIONS, W/ 4#-. ? WHAT SIZE WIRE? |
| | PLEASE ALSO NOTE, DETAIL FOR 3-2/0`S?? |
| | PLEASE CORRELATE. CLARIFY CONDUCTORS. |
| | |
| | 4)NOTE: PLEASE NOTE NO LOAD CALCULATIONS |
| | FORFOR PANEL "UPP"?? E-6 SHOWS EXSIT- |
| | -ING AND E-3 SHOWS PART OF NEW RISER? |
| | PLEASE CALRIFY. |
| | |
| | 5)NOTE: PLEASE NOTE THAT RISER NOTE ON |
| | E-3 MENTIONS, RISER IN "MAIDS CLOSET"??? |
| | PLEASE SEE 384-7 AND 110-26 FOR |
| | EQUIPMENT BEING INSTALLED THESE LOCATION |
| | -S. PLEASE NOTE DEDICATED ELECTRICAL |
| | SPACE AND IGNITIBLE STORAGE. |
| | |
| | 6)NOTE: PLEASE SHOW LOCATION OF THIS |
| | ROOM ON PLAN. PLEASE SHOW LOCATION AND |
| | MOUNTING DETAIL FOR TRANSFORMER. |
| | SEE 450-9,4502-13,450-21. |
| | |
| | 7)NOTE: PLEASE CLARIFY PANEL "UPP". |
| | MAIN BRKR? MLO? PLEASE NOTE LIGHTING |
| | PANEL HAVING MAIN BRKR REQ`D FROM |
| | TRANSFORMER. |
| | |
| | 8)NOTE: PLEASE NOTE THAT ALL CONTINUOUS |
| | LOADS ARE TO BE SHOWN AT 125%. |
| | |
| | 9)NOTE: PLEASE PROVIDE A COPY OF |
| | CONTRACT TO VERIFY VALUE FOR COMPLET |
| | SCOPE OF WORK. PLEASE NOTE ALL LABOR |
| | AND MATERIALS ARE TO BE INCLUDED FOR |
| | PERMIT VALUATION. 104.6.5 FBCAC |
| | CITY OF WEST PALM BEACH LOCAL ADMIN |
| | AMENDMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |