| 2002-04-04 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FOR PERMIT APPLICATIONS RECIEVED BEFORE |
| | MARCH 1, 2002 EITHER STANDARD BUILDING |
| | CODE 1997 OR FLORIDA BUILDING CODE 2001 |
| | MAY BE USED.AS SHEET S14, GENERAL |
| | NOTES REFERS TO STANDARD BUILDING CODE |
| | 1997 THE PLANS HAVE BEEN REVIEWED FOR |
| | COMPLIANCE WITH THAT CODE. |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PLANS SHALL BE ASSESSED BY PALM |
| | BEACH COUNTY BUILDING DIVISION FOR |
| | IMPACT FEES, PLANS STAMPED BY THEM AND A |
| | COPY OF THE RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE ELECTRICAL PLAN REVIEW COMMENT #9 |
| | SHALL BE ADDRESSED IN RESPECT OF THE |
| | VALUE AND SCOPE OF WORK. |
| | |
| | 4) ARCHITECTURAL SPECIFICATION.ALL |
| | REFERENCES TO 1991 STANDARD BUILDING |
| | CODE SHALL BE AMENDED TO READ |
| | 1997 STANDARD BUILDING CODE. FOR EXAMPLE |
| | SECTION 03450 PART 1.03C, SECTION 03455 |
| | PART 1.04A AND SECTION 07241 PART 1.03D |
| | |
| | 5) SBC* 1804.2.2SHEET S14, FOUNDATION |
| | NOTES.SUBMIT A SOIL REPORT TO VERIFY |
| | THE ASSUMED BEARING PRESSURE OF 3000 PSF |
| | |
| | 6) SBC* 1606.4DOOR PRODUCT APPROVAL. |
| | THE SUBMITTED MIAMI-DADE NOTICE OF |
| | ACCEPTANCE NO 97/0903.12 EXPIRED ON |
| | 12/31/2001 AND INCLUDES SHEET 1 ONLY. |
| | SUBMIT COMPLETE AND VALID PRODUCT |
| | APPROVALS FOR THE NEW EXTERNAL DOORS. |
| | |
| | 7) SBC* 1606.4SHEET A-5 AND SPECIF'N |
| | SECTION 07810 - SKYLIGHT RENOVATION. |
| | THE REPLACEMENT GLAZING SHALL BE |
| | DESIGNED AND TESTED IN ACCORDANCE WITH |
| | SBCCI SSTD 12-99, TEST STANDARD FOR |
| | DETERMINING IMPACT RESISTANCE FROM |
| | WINDBORNE DEBRIS.SUBMIT DETAILS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 8) SBC 1007.3STAIR TREADS AND RISERS. |
| | DETAILS 3/S9 AND 10/A11.THE HEIGHT OF |
| | THE RISERS (R) SHALL NOT EXCEED 7-3/4" |
| | (TREAD (T) EXCEEDS 9", AND IS COMPLIANT) |
| | ALSO, THE RELATIONSHIP 2R+T SHALL NOT BE |
| | LESS THAN 24" OR MORE THAN 25". ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 9) FL ACC CODE 4.32.4FRONT DESK |
| | (SHEET 1D.11).THE HEIGHT OF THE NEW |
| | FRONT DESK SHALL BE BETWEEN 28" TO 34" |
| | ABOVE FINISH FLOOR LEVEL. |
| | |
| | 10) FL ACC CODE 4.17.6GRAB BARS. |
| | ANNOTATE SHEET ID.16 TO DEMONSTRATE |
| | COMPLIANCE WITH THE GRAB BAR LENGTH AND |
| | POSITIONING REQUIREMENTS AS SHOWN IN |
| | FIGURE 30. |
| | |
| | 11) FL ACC CODE 4.15DRINKING FOUNTAINS |
| | SHEET ID.2.THE NEW WATER (DRINKING) |
| | FOUNTAINS SHALL HAVE CLEARANCES AND |
| | SPOUT HEIGHT IN ACCORDANCE WITH FIG. 27. |
| | ANNOTATE THE PLANS TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 12) FL ACC CODE 4.8.5(2)NEW RAMP |
| | ADJACENT THE RESTAURANT AND NEW RAMP IN |
| | CORRIDOR 116 (SHEET ID.17).THE RAMP |
| | HANDRAILS SHALL EXTEND NOT LESS THAN 18" |
| | BEYOND THE SLOPED SECTION AT BOTH THE |
| | TOP AND BOTTOM OF THE RAMP (REF FIG. 17) |
| | |
| | 13) FL ACC CODE 4.9.4(2)SHEET ID.17. |
| | THE BOTTOM OF THE STAIR HANDRAIL SHALL |
| | CONTINUE TO SLOPE, BEYOND THE LEADING |
| | EDGE OF THE BOTTOM RISER, FOR A DISTANCE |
| | EQUAL TO THE DEPTH OF ONE TREAD AND THEN |
| | EXTEND HORIZONTALLY FOR A FURTHER 12". |
| | (REF FIG. 19C) |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |