Plan Review Notes
Plan Review Notes For Permit 02021641
Permit Number 02021641
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FOR PERMIT APPLICATIONS RECIEVED BEFORE
 MARCH 1, 2002 EITHER STANDARD BUILDING
 CODE 1997 OR FLORIDA BUILDING CODE 2001
 MAY BE USED.AS SHEET S14, GENERAL
 NOTES REFERS TO STANDARD BUILDING CODE
 1997 THE PLANS HAVE BEEN REVIEWED FOR
 COMPLIANCE WITH THAT CODE.
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PLANS SHALL BE ASSESSED BY PALM
 BEACH COUNTY BUILDING DIVISION FOR
 IMPACT FEES, PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE ELECTRICAL PLAN REVIEW COMMENT #9
 SHALL BE ADDRESSED IN RESPECT OF THE
 VALUE AND SCOPE OF WORK.
  
 4) ARCHITECTURAL SPECIFICATION.ALL
 REFERENCES TO 1991 STANDARD BUILDING
 CODE SHALL BE AMENDED TO READ
 1997 STANDARD BUILDING CODE. FOR EXAMPLE
 SECTION 03450 PART 1.03C, SECTION 03455
 PART 1.04A AND SECTION 07241 PART 1.03D
  
 5) SBC* 1804.2.2SHEET S14, FOUNDATION
 NOTES.SUBMIT A SOIL REPORT TO VERIFY
 THE ASSUMED BEARING PRESSURE OF 3000 PSF
  
 6) SBC* 1606.4DOOR PRODUCT APPROVAL.
 THE SUBMITTED MIAMI-DADE NOTICE OF
 ACCEPTANCE NO 97/0903.12 EXPIRED ON
 12/31/2001 AND INCLUDES SHEET 1 ONLY.
 SUBMIT COMPLETE AND VALID PRODUCT
 APPROVALS FOR THE NEW EXTERNAL DOORS.
  
 7) SBC* 1606.4SHEET A-5 AND SPECIF'N
 SECTION 07810 - SKYLIGHT RENOVATION.
 THE REPLACEMENT GLAZING SHALL BE
 DESIGNED AND TESTED IN ACCORDANCE WITH
 SBCCI SSTD 12-99, TEST STANDARD FOR
 DETERMINING IMPACT RESISTANCE FROM
 WINDBORNE DEBRIS.SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 8) SBC 1007.3STAIR TREADS AND RISERS.
 DETAILS 3/S9 AND 10/A11.THE HEIGHT OF
 THE RISERS (R) SHALL NOT EXCEED 7-3/4"
 (TREAD (T) EXCEEDS 9", AND IS COMPLIANT)
 ALSO, THE RELATIONSHIP 2R+T SHALL NOT BE
 LESS THAN 24" OR MORE THAN 25". ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 9) FL ACC CODE 4.32.4FRONT DESK
 (SHEET 1D.11).THE HEIGHT OF THE NEW
 FRONT DESK SHALL BE BETWEEN 28" TO 34"
 ABOVE FINISH FLOOR LEVEL.
  
 10) FL ACC CODE 4.17.6GRAB BARS.
 ANNOTATE SHEET ID.16 TO DEMONSTRATE
 COMPLIANCE WITH THE GRAB BAR LENGTH AND
 POSITIONING REQUIREMENTS AS SHOWN IN
 FIGURE 30.
  
 11) FL ACC CODE 4.15DRINKING FOUNTAINS
 SHEET ID.2.THE NEW WATER (DRINKING)
 FOUNTAINS SHALL HAVE CLEARANCES AND
 SPOUT HEIGHT IN ACCORDANCE WITH FIG. 27.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 12) FL ACC CODE 4.8.5(2)NEW RAMP
 ADJACENT THE RESTAURANT AND NEW RAMP IN
 CORRIDOR 116 (SHEET ID.17).THE RAMP
 HANDRAILS SHALL EXTEND NOT LESS THAN 18"
 BEYOND THE SLOPED SECTION AT BOTH THE
 TOP AND BOTTOM OF THE RAMP (REF FIG. 17)
  
 13) FL ACC CODE 4.9.4(2)SHEET ID.17.
 THE BOTTOM OF THE STAIR HANDRAIL SHALL
 CONTINUE TO SLOPE, BEYOND THE LEADING
 EDGE OF THE BOTTOM RISER, FOR A DISTANCE
 EQUAL TO THE DEPTH OF ONE TREAD AND THEN
 EXTEND HORIZONTALLY FOR A FURTHER 12".
 (REF FIG. 19C)
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499