 ***************PROVISO!*****************
  
 PLEASE NOTE THE FOLLOWING AND INSTALL AS
 PER APPROPRIATE CODE ARTICLES.
  
 1] SUPPLEMENTAL ELECTRODES AS REQUIRED
 BY 250-56 AND RELATED ARTICLES.
  
 2] CORRECT THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR AS PER 250-66.
  
 3] THE 2" EMT FEEDER CONDUIT MUST
 CONTAIN A #6 EQUIPMENT GROUND AS PER
 250-118
 CITY AMENDMENTS>250-122 N.E.C.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW