| 2002-03-01 00:00:00 | | | | | | | ***************PROVISO!***************** | | | | | | PLEASE NOTE THE FOLLOWING AND INSTALL AS | | | PER APPROPRIATE CODE ARTICLES. | | | | | | 1] SUPPLEMENTAL ELECTRODES AS REQUIRED | | | BY 250-56 AND RELATED ARTICLES. | | | | | | 2] CORRECT THE SIZE OF THE GROUNDING | | | ELECTRODE CONDUCTOR AS PER 250-66. | | | | | | 3] THE 2" EMT FEEDER CONDUIT MUST | | | CONTAIN A #6 EQUIPMENT GROUND AS PER | | | 250-118 | | | CITY AMENDMENTS>250-122 N.E.C. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|