| 2003-02-19 00:00:00 | ************** PROVISO/NOTES ********** | | | | | | 1)NOTE: PLEASE SEE LOAD CALCUALTIONS | | | DONE BY ENGINEER AND ELECTRICAL | | | CONTRACTOR. PLEASE NOTE, AHU HEAT IS | | | DERATED AT 65% AND THEN AGAIN @ 40%?? | | | PLEASE SEE NEC 220 FOR LOAD CALCS FOR | | | DERATING. CAN NOT BE DERATED TWICE. | | | PLEASE ALSO SEE LOAD CALCS DONE BY | | | ELECTRICAL CONTRACTOR. PLEASE NOTE, | | | AHU HEAT IS DERATED @40%.? CAN BE DONE | | | AT 100% OR DERATED AT 65%. PLEASE ALSO | | | SEE 3WATTS PER SQ FT BY ENGINEER AND | | | CONT., PLEASE RECONFIGURE LOAD CALCS. | | | ADDITION IS SHOWN AS BEING AS LARGE | | | AS EXISTING RES? | | | | | | 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE | | | PER 210-12. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVEIW BEFORE ANY | | | ROUGH ELECTRICAL INSPECTION OS CALLED | | | IN. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-6659-8096 EXT 8372 |
|