Plan Review Notes
Plan Review Notes For Permit 02021497
Permit Number 02021497
Review Stop E
Sequence Number 2
Notes
Date Text
2002-10-29 00:00:00****************** UNSAT **********
  
 1)NOTE: PLEASE NOTE, FIRST TWO NOTES
 FROM FIRST REVIEW WERE NOT ADDRESSED?
 PLEASE SUBMIT A COMPLETED LOAD CALCULAT-
 ION FOR NEW AS-WELL AS EXISTING PER
 220-3-C-1. PANEL SHOWN, SHOWS NEW A/C
 SYSTEM AND NEW CIRCUIT W/OUT SHOWING
 SIZE OF EXISTING SERVICE?
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372