| 2002-02-28 00:00:00 | ************* UNSAT ******************* |
| | |
| | 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS |
| | ARE NOT COMPLETE. PLEASE SEE 220-3-C-1 |
| | PLEASE SHOW EXSITING AS WELL AS NEW. |
| | |
| | 2)NOTE: PLEASE NOTE NO "EXISTING" RISER |
| | DIAGRAM WAS SUBMITTED. PLEASE CALRIFY |
| | SIZE OF EXSITING SERVICE AND LOADS. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5)NOTE : PLEASE CLARIFY IF WASHER/DRYER |
| | SHOWN AND WHAT APPEARS TO BE HWH IS |
| | EXISTING AND JUST BEING MOVED TO NEW |
| | LOCATION OR ARE THEY NEW? NOT SHOWN ON |
| | PANEL SCHEDULE. |
| | |
| | 6)NOTE: PLEASE NOTE MISSING EGRESS |
| | LIGHTING? PLEASE CLARIFY IF FANS SHOWN |
| | ARE FAN/LT COMBO. 210-70 |
| | |
| | 7)NOTE: PLEASE NOTE MISSING GFI OUTLET |
| | FOR A/C CU. PER 309.2 OF THE MECH CODE. |
| | |
| | 8)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | AHU IN ATTIC. PER 210-63 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |