Plan Review Notes For Permit 02021497
Permit Number 02021497
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-28 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 ARE NOT COMPLETE. PLEASE SEE 220-3-C-1
 PLEASE SHOW EXSITING AS WELL AS NEW.
  
 2)NOTE: PLEASE NOTE NO "EXISTING" RISER
 DIAGRAM WAS SUBMITTED. PLEASE CALRIFY
 SIZE OF EXSITING SERVICE AND LOADS.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE : PLEASE CLARIFY IF WASHER/DRYER
 SHOWN AND WHAT APPEARS TO BE HWH IS
 EXISTING AND JUST BEING MOVED TO NEW
 LOCATION OR ARE THEY NEW? NOT SHOWN ON
 PANEL SCHEDULE.
  
 6)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING? PLEASE CLARIFY IF FANS SHOWN
 ARE FAN/LT COMBO. 210-70
  
 7)NOTE: PLEASE NOTE MISSING GFI OUTLET
 FOR A/C CU. PER 309.2 OF THE MECH CODE.
  
 8)NOTE: PLEASE NOTE MISSING OUTLET FOR
 AHU IN ATTIC. PER 210-63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372