Plan Review Notes
Plan Review Notes For Permit 02021488
Permit Number 02021488
Review Stop M
Sequence Number 3
Notes
Date Text
2002-06-21 00:00:00DENIED:MECHANICAL PERMIT 02021493
  
 ITEMS#1 & 3 FROM REVIEW DATED 6/5/02
 NOT ADDRESSED.
  
 1. AXILIARY DRAIN SHALL TERMINATE AT A
 CONSPICUOUS POINT.PLEASE CLARIFY
 HOW THE AXUILIARY DRAIN LINE RUN WITH
 & TERMINATING AT THE SAME POINT AS
 THE PRIMARY DRAIN IS A "CONSPICUOUS
 POINT".
  
 3. SHOW COMPLIANCE WITH 1997 SMC 704,
 FOR COMBUSTION AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.