| Plan Review Notes For Permit 02021488 |
| Permit Number |
02021488 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-06-27 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NOT ALL NOTES FROM THE FIRST AND SECOND | | | REVIEWS HAVE BEEN CORRECTED.PLEASE | | | CORRECT THEM AND THE FOLLOWING AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | NEED THE RATING NOT A NOTE. | | | | | | 2} CORRECT THE MARKING ON THE SERVICE | | | GEAR,"TMB","TLO". | | | | | | 3} LIST THE OCP AND WIRE SIZE FOR PANEL | | | "C" ON PANEL"B"SCHEDULE.INCLUDE IN THE | | | CALCULATION FOR "B" PANEL. | | | | | | 4} PLEASE NOTE THE OCP FOR THE 5KW HEAT | | | STRIP EXCEEDS 150%. | | | | | | 5} SMOKE DETECTORS PER 2-2.1.1.1(BED RMS | | | 3 & 4). | | | | | | 6} GFI TO BE INSTALLED IN FRONT OF THE | | | RESIDENCE PER 210-52(E). | | | | | | 7} THE RERIGERATOR CIRCUIT IN PANEL "A" | | | IS SHOWN AS 3KW ON A SINGLE POLE 20AMP | | | BREAKER EXCEEDING 80% OF THE BREAKER | | | RATING.PLEASE CORRECT. | | | | | | 8} ATTIC ACCESS FOR AHU #2 MUST COMPLY | | | WITH 210-70(A)(3) & 210-63.PLEASE | | | INDICATE SAME ON PLANS. | | | | | | 9} THE PLAN SHOWS A DISCONNECT NEXT TO | | | THE METER AND NOT ON THE RISER,PLEASE | | | CLARIFY ON THE PLAN. | | | | | | 10} NOTE THE LIVING ROOM IS MISSING A | | | RECEPTACLE PER 210-52(A)(1). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|