Plan Review Notes
Plan Review Notes For Permit 02021488
Permit Number 02021488
Review Stop E
Sequence Number 3
Notes
Date Text
2002-06-27 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOT ALL NOTES FROM THE FIRST AND SECOND
 REVIEWS HAVE BEEN CORRECTED.PLEASE
 CORRECT THEM AND THE FOLLOWING AND
 RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 NEED THE RATING NOT A NOTE.
  
 2} CORRECT THE MARKING ON THE SERVICE
 GEAR,"TMB","TLO".
  
 3} LIST THE OCP AND WIRE SIZE FOR PANEL
 "C" ON PANEL"B"SCHEDULE.INCLUDE IN THE
 CALCULATION FOR "B" PANEL.
  
 4} PLEASE NOTE THE OCP FOR THE 5KW HEAT
 STRIP EXCEEDS 150%.
  
 5} SMOKE DETECTORS PER 2-2.1.1.1(BED RMS
 3 & 4).
  
 6} GFI TO BE INSTALLED IN FRONT OF THE
 RESIDENCE PER 210-52(E).
  
 7} THE RERIGERATOR CIRCUIT IN PANEL "A"
 IS SHOWN AS 3KW ON A SINGLE POLE 20AMP
 BREAKER EXCEEDING 80% OF THE BREAKER
 RATING.PLEASE CORRECT.
  
 8} ATTIC ACCESS FOR AHU #2 MUST COMPLY
 WITH 210-70(A)(3) & 210-63.PLEASE
 INDICATE SAME ON PLANS.
  
 9} THE PLAN SHOWS A DISCONNECT NEXT TO
 THE METER AND NOT ON THE RISER,PLEASE
 CLARIFY ON THE PLAN.
  
 10} NOTE THE LIVING ROOM IS MISSING A
 RECEPTACLE PER 210-52(A)(1).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392