| Plan Review Notes For Permit 02021488 |
| Permit Number |
02021488 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-06-06 00:00:00 | | | | | | | 1.AS PER 1997 SMC AUXILIARY DRAIN | | | SHALL TERMINATE AT A CONSPICUOUS | | | POINT TO SERVICE AS AN ALARM THAT | | | THE PRIMARY DRAIN IS RESTRICTED. | | | PLEASE CLARIFY HOW THE AUXILARY | | | DRAIN LINE RUN WITH & TERMINATING | | | AT THE SAME POINT AS THE PRIMARY | | | DRAIN IS A "CONSPICUOUS POINT". | | | | | | 2.PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE GAS FIREPLACE, | | | GRILL W/HOOD & VENTLESS F.P. SHOWN | | | ON PLAN SHEET A-3. | | | | | | 3.PROVIDE INFORMATION ON VENT FOR THE | | | GAS DRYER & SHOW COMPLIANCE WITH | | | CHAPTER 7 OF THE 1997 SMC. | | | | | | 4.AHU'S SHALL HAVE ADEQUATE ACCESS FOR | | | MAINTENANCE & SERVICE AS PER 1997 | | | SMC 304.2 & 304.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|