Plan Review Notes
Plan Review Notes For Permit 02021488
Permit Number 02021488
Review Stop M
Sequence Number 2
Notes
Date Text
2002-06-06 00:00:00 
  
 1.AS PER 1997 SMC AUXILIARY DRAIN
 SHALL TERMINATE AT A CONSPICUOUS
 POINT TO SERVICE AS AN ALARM THAT
 THE PRIMARY DRAIN IS RESTRICTED.
 PLEASE CLARIFY HOW THE AUXILARY
 DRAIN LINE RUN WITH & TERMINATING
 AT THE SAME POINT AS THE PRIMARY
 DRAIN IS A "CONSPICUOUS POINT".
  
 2.PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE GAS FIREPLACE,
 GRILL W/HOOD & VENTLESS F.P. SHOWN
 ON PLAN SHEET A-3.
  
 3.PROVIDE INFORMATION ON VENT FOR THE
 GAS DRYER & SHOW COMPLIANCE WITH
 CHAPTER 7 OF THE 1997 SMC.
  
 4.AHU'S SHALL HAVE ADEQUATE ACCESS FOR
 MAINTENANCE & SERVICE AS PER 1997
 SMC 304.2 & 304.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.