| 2002-06-05 00:00:00 | ***************** UNSAT ************* |
| | |
| | PLEASE NOTE THAT NO ALL NOTES FORM FIRST |
| | REVIEW WERE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE 310-15 FOR SIZING OF |
| | 350MCM FOR SERVICE. A 400A SERVICE IS |
| | SHOWN.(NOTE#4 FIRST REVIEW) |
| | |
| | 2)NOTE: PLEASE NOTE THAT PANEL "B" STILL |
| | DOES NOT SHOW OCP FOR FEEDING PANEL "C" |
| | IF PANEL "B" HAS FEED THROUGH LUGS, THEN |
| | WIRE SIZE NEEDS TO INCREASE TO MEET MAIN |
| | OCP OF 200AMPS. (NOTE #6 FIRST REVIEW) |
| | LOAD CALCS NOT INCLUDED ON "B" FOR "C"?? |
| | 3)NOTE: PLEASE NOTE PLANS STILL MISSING |
| | OUTLET SPACING TO MEET 210-52/210-52H |
| | PLEASE ALSO NOTE KITCHEN LAYOUT FOR |
| | COUNTERSPACE HAS CHANGED. PLEASE NOTE |
| | MISSING GFI/OUTLET(S) PER210-52-C-1. |
| | (NOTE# 9 FIRST REVIEW) |
| | |
| | 4)NOTE: PLEASE NOTE PANEL SCHEDULE SHOWS |
| | BEDROOM CIRCUITS, BUT NO MENTION OF |
| | ARC FAULT PROTECTION PER 210-12. CAN BE |
| | A NOTE ON PLANS. |
| | |
| | 5)NOTE: PLEASE NOTE SMOKE DETECTORS |
| | STILL MISSING PER NFPA-72. MISSING IN |
| | VICINITY OF STAIRS LEADING TO ABOVE FLR. |
| | 2-5.2.1.4 PLEASE ALSO NOTE A SD HAS BEEN |
| | PLACED IN MASTER BATH. PLEASE NOTE THAT |
| | THIS IS NOT PERMITTED PER 2-5.2.1.6. |
| | PLEASE NOTE THERE A FEW SD`S SHOWN THAT |
| | GO ABOVE AND BEYOND WHAT IS REQ`D. |
| | PLEASE NOTE, IF SHOWN ON PLANS THEN |
| | THEY WILL BE REQ`D TO BE INSTALLED OR |
| | PLANS MAY NEED TO BE REVISED AT A LATER |
| | DATE. JUST A NOTE. |
| | (NOTE#2 FROM FIRST REVIEW) |
| | |
| | 6)NOTE: PLEASE NOTE OCP FOR 5KW HEAT |
| | STRIP SHOWN AT 50AMPS? PLEASE VERIFY. |
| | MAX OCP 150%? |
| | |
| | PLEASE SUBMIT THE ABOVE FOR REVIEW. |