2002-06-05 00:00:00***************** UNSAT *************
  
 PLEASE NOTE THAT NO ALL NOTES FORM FIRST
 REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE SEE 310-15 FOR SIZING OF
 350MCM FOR SERVICE. A 400A SERVICE IS
 SHOWN.(NOTE#4 FIRST REVIEW)
  
 2)NOTE: PLEASE NOTE THAT PANEL "B" STILL
 DOES NOT SHOW OCP FOR FEEDING PANEL "C"
 IF PANEL "B" HAS FEED THROUGH LUGS, THEN
 WIRE SIZE NEEDS TO INCREASE TO MEET MAIN
 OCP OF 200AMPS. (NOTE #6 FIRST REVIEW)
 LOAD CALCS NOT INCLUDED ON "B" FOR "C"??
 3)NOTE: PLEASE NOTE PLANS STILL MISSING
 OUTLET SPACING TO MEET 210-52/210-52H
 PLEASE ALSO NOTE KITCHEN LAYOUT FOR
 COUNTERSPACE HAS CHANGED. PLEASE NOTE
 MISSING GFI/OUTLET(S) PER210-52-C-1.
 (NOTE# 9 FIRST REVIEW)
  
 4)NOTE: PLEASE NOTE PANEL SCHEDULE SHOWS
 BEDROOM CIRCUITS, BUT NO MENTION OF
 ARC FAULT PROTECTION PER 210-12. CAN BE
 A NOTE ON PLANS.
  
 5)NOTE: PLEASE NOTE SMOKE DETECTORS
 STILL MISSING PER NFPA-72. MISSING IN
 VICINITY OF STAIRS LEADING TO ABOVE FLR.
 2-5.2.1.4 PLEASE ALSO NOTE A SD HAS BEEN
 PLACED IN MASTER BATH. PLEASE NOTE THAT
 THIS IS NOT PERMITTED PER 2-5.2.1.6.
 PLEASE NOTE THERE A FEW SD`S SHOWN THAT
 GO ABOVE AND BEYOND WHAT IS REQ`D.
 PLEASE NOTE, IF SHOWN ON PLANS THEN
 THEY WILL BE REQ`D TO BE INSTALLED OR
 PLANS MAY NEED TO BE REVISED AT A LATER
 DATE. JUST A NOTE.
 (NOTE#2 FROM FIRST REVIEW)
  
 6)NOTE: PLEASE NOTE OCP FOR 5KW HEAT
 STRIP SHOWN AT 50AMPS? PLEASE VERIFY.
 MAX OCP 150%?
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 ONCE AGAIN, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW