Plan Review Notes
Plan Review Notes For Permit 02021488
Permit Number 02021488
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-08 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 THIS NOTE IS ON THE PLANS AND ARE FROM
 PREVIOUS REVIEW NOTES? PLEASE ACTUALLY
 SUBMIT THE RATINGS.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 MISSING IN MANY LOCATIONS. PLEASE NOTE
 THAT ROOMS WITH BATHS AND/OR CLOSETS ARE
 ADAPTABLE SLEEPING RMS.
  
 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS 350 MCM BEING INSTALLED. PLEASE
 NOTE THAT PER 310-15 350MCM IS GOOD FOR
 A 350A SERVICE. PLEASE NOTE THAT TWO,
 200A PANELS ARE GOING IN?
  
 5)NOTE: PLEASE NOTE THAT THERE IS AN
 EQUIPMENT GROUNDING CONDUCTOR SHOWN
 BETWEEN GUTTER AND MAIN DISC #1. PLEASE
 NOTE THAT THIS IS PARALLELING THE
 NEUTRAL? PLEASE REMOVE.
  
 6)NOTE: PLEASE NOTE THAT PANEL "B", SHOW
 -S FEED TO PANEL "C" BUT DOES NOT SHOW
 OCP.? FEEDERS ARE NOTED ON RISER DIAGRAM
 .
  
 7)NOTE: PLEASE NOTE THAT PLAN SHOW FOUR
 A/C COND UNITS AND ONLY 3 SETSARE
 SHOWN ON PANEL SCHEDULES AND LOAD CALCS.
  
 8)NOTE: PLEASE SHOW ROOM DESIGNATION
 ON PLANS.
  
 9) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING IN ENTIRE LIVING ROOM?
 AND A FEW OTHERS.
  
 10)PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 MISSING FRONT.
  
 11)NOTE: PLEASE NOTE MISSING REC FOR
 AHU #1 PER MECH CODE.309.2
  
 12)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 BATHS ARE NOW SHOWN AS 15A AND #14??
  
 13)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS ON PLANS PER 210-12. CODE WENT
 INTO EFFECT 1/1/2002.
  
 14)NOTE: PLEASE NOTE 60A OCP SHOWN FOR
 5KW HEAT FOR A/C SYSTEM ON PANEL "C".
 PLEASE CORRECT.
  
 15)NOTE: PLEASE CLARIFY 3KW FOR A SINGLE
 POLE 20A BRKR FOR FRIG CIRCUIT.
 PLEASE NOTE 80% MAX LOAD FOR BRANCH
 CIRCUIT AND RATING OF BRKR.PER 384
  
 16)NOTE: PLEASE SHOW OUTLETS ABOVE BATH
 AS GFI/GFI PROTECTED. 210-8
  
 17)NOTE: PLEASE NOTE REC AND LT REQ`D
 FOR AHU`S #2,3, IN ATTIC.
 ATTIC ACCESS.PER 210-63/210-70 AND 309.2
 NEC AND MECH CODE.
  
 18)NOTE: PLEASE NOTE THAT PLANS ONLY
 SHOWS ONE MAIN NEXT TO METER. PLEASE
 SHOW BOTH MAINS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372