| Date |
Text |
| 2002-03-08 00:00:00 | ***************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | THIS NOTE IS ON THE PLANS AND ARE FROM |
| | PREVIOUS REVIEW NOTES? PLEASE ACTUALLY |
| | SUBMIT THE RATINGS. |
| | |
| | 2) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | MISSING IN MANY LOCATIONS. PLEASE NOTE |
| | THAT ROOMS WITH BATHS AND/OR CLOSETS ARE |
| | ADAPTABLE SLEEPING RMS. |
| | |
| | 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. |
| | MISSING BLDG/FOOTER STEEL. |
| | |
| | 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | SHOWS 350 MCM BEING INSTALLED. PLEASE |
| | NOTE THAT PER 310-15 350MCM IS GOOD FOR |
| | A 350A SERVICE. PLEASE NOTE THAT TWO, |
| | 200A PANELS ARE GOING IN? |
| | |
| | 5)NOTE: PLEASE NOTE THAT THERE IS AN |
| | EQUIPMENT GROUNDING CONDUCTOR SHOWN |
| | BETWEEN GUTTER AND MAIN DISC #1. PLEASE |
| | NOTE THAT THIS IS PARALLELING THE |
| | NEUTRAL? PLEASE REMOVE. |
| | |
| | 6)NOTE: PLEASE NOTE THAT PANEL "B", SHOW |
| | -S FEED TO PANEL "C" BUT DOES NOT SHOW |
| | OCP.? FEEDERS ARE NOTED ON RISER DIAGRAM |
| | . |
| | |
| | 7)NOTE: PLEASE NOTE THAT PLAN SHOW FOUR |
| | A/C COND UNITS AND ONLY 3 SETSARE |
| | SHOWN ON PANEL SCHEDULES AND LOAD CALCS. |
| | |
| | 8)NOTE: PLEASE SHOW ROOM DESIGNATION |
| | ON PLANS. |
| | |
| | 9) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING IN ENTIRE LIVING ROOM? |
| | AND A FEW OTHERS. |
| | |
| | 10)PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | MISSING FRONT. |
| | |
| | 11)NOTE: PLEASE NOTE MISSING REC FOR |
| | AHU #1 PER MECH CODE.309.2 |
| | |
| | 12)NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | BATHS ARE NOW SHOWN AS 15A AND #14?? |
| | |
| | 13)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | CIRCUITS ON PLANS PER 210-12. CODE WENT |
| | INTO EFFECT 1/1/2002. |
| | |
| | 14)NOTE: PLEASE NOTE 60A OCP SHOWN FOR |
| | 5KW HEAT FOR A/C SYSTEM ON PANEL "C". |
| | PLEASE CORRECT. |
| | |
| | 15)NOTE: PLEASE CLARIFY 3KW FOR A SINGLE |
| | POLE 20A BRKR FOR FRIG CIRCUIT. |
| | PLEASE NOTE 80% MAX LOAD FOR BRANCH |
| | CIRCUIT AND RATING OF BRKR.PER 384 |
| | |
| | 16)NOTE: PLEASE SHOW OUTLETS ABOVE BATH |
| | AS GFI/GFI PROTECTED. 210-8 |
| | |
| | 17)NOTE: PLEASE NOTE REC AND LT REQ`D |
| | FOR AHU`S #2,3, IN ATTIC. |
| | ATTIC ACCESS.PER 210-63/210-70 AND 309.2 |
| | NEC AND MECH CODE. |
| | |
| | 18)NOTE: PLEASE NOTE THAT PLANS ONLY |
| | SHOWS ONE MAIN NEXT TO METER. PLEASE |
| | SHOW BOTH MAINS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |