| 2002-04-06 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 02021488 |
| | 7645 HAWKS LANDING |
| | CONT: CRIBB |
| | TEL: 689-6900 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | |
| | 1) DESIGN CRITERIA SHEET NOT SEALED BY |
| | THE ARCHETECT OF RECORD, DOCUMENTS FOR |
| | PUBLIC RECORD SHALL BE SIGNED & SEALED |
| | 61G1-16.003 |
| | 2)- CLOSPY DOOR (GARAGE DOOR) REPORT |
| | INDICATED OR WAS CIRCLED INDICATING THE |
| | USE OF THE 4050 MODEL DOOR, THIS DOOR |
| | DOESN'T MEET THE POSITIVE OR NEGATIVE |
| | PRESSURES, ALSO WILL NOT MEET THE |
| | REQUIREMENTS OF THE 16'-0" X 8'-0" |
| | OPENING. |
| | 3)- THE ARCH. SHALL INDICATE AS TO WHICH |
| | MULLION IS TO BE USED IN CONJUNCTION |
| | WITH THE DIFFERENT WINDOW CONFIGURATIONS |
| | HORIZONTAL & VERTICAL MULLIONS. |
| | 4)- PRODUCT APPROVAL FOR CASEMENT WINDOW |
| | BUT NOT FOR SINGLE HUNG WINDOWS. |
| | 5)- SHEET A-3&4 INDICATE THE USE OF A |
| | CIRCULAR STAIR TO A LOFT. PROVIDE THE |
| | MANUFACTURERS SPEC FOR COMPARISON TO |
| | SBC 1007.8.2. |
| | 6)- SBC 104.2.2 ADDITIONAL INFORMATION |
| | SHALL BE REQUIRED ON THE LOFT IN THE |
| | LIBRARY. A CUT SECTION THROUGH WOULD |
| | GIVE BETTER DETAIL. SBC 503.2.3 MEZANINE |
| | SBC 1203.2.1 OCCUPIABLE ROOMS MINIMUM |
| | CEILING HEIGTH OF 7'-6" ARE CONCERNS. |
| | INDICATE STRUCTURAL DETAILS? |
| | 7)- SBC 104.2.2 MISSING INFORMATION ON |
| | THE FIRE PLACE &CHIMNEY IN THE LIVING |
| | ROOM, THE VENTLESS FIREPLACE IN THE |
| | COVERED PORCH AND THE GRILL. |
| | 8)-SHEET A-8 DISCREPANCY THE TRUSS |
| | STRAP SCHEDULE INDICATES THE USE OF USP |
| | FOR TRUSS ANCHORS VS THE DETAILS WHICH |
| | SPECIFY SEMCO WHICH IS NO LONGER IN |
| | BUSINESS?WHAT ARE THE NEW CATALOG #? |
| | 9)- SHEET A-8DEAIL A & B INDICATE THE |
| | USE OF MULTIPLE OR SEVERAL STRAPS IN |
| | A CONCRETE BEAM OR CMU. USP REQUIRES A |
| | DERATING WHEN STRAPS ARE PLACED CLOSER |
| | THAN 8" BECAUSE OF THE CONE PILL OUT |
| | AFFECT. HOW MUCH DERATING DOES USP |
| | REQUIRE? |
| | 10)- PLANS ARE TO BE ASSESSED BY PALM |
| | BEACH COUNTY FOR IMPACT FEES BEFORE |
| | THE ISSUANCE OF A PERMIT. |
| | 11)- ADDITIONAL FEES DUE! |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |