| Plan Review Notes For Permit 02021424 |
| Permit Number |
02021424 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-06-19 00:00:00 | | | | ONLY ONE SET OF ENERGY CALCS SUBMITTED | | | & NO MANUAL J CALCULATIONS SUBMITTED. | | | | | | AS PER 1997 SMC 304.4.1, ACCESS OPENING | | | FOR EQUIPMENT IN THE ATTIC SHALL BE NO | | | LESS THAN 22" X 36" CONTINUOUS FROM THE | | | OPENING TO ITS CONTROLS.AS PER COUNTY | | | WIDE AMMENDMENTS 304.4.2 EQUIPMENT IN | | | THE ATTIC MUST ALSO HAVE AN ACCESSIBLE | | | DISCONNECT SWITCH & A 110-120 VOLT A/C | | | GROUNDING TYPE CONVENIENCE OUTLET & A | | | LIGHT ON THE SERVICE SIDE OF THE EQUIP. | | | CONTROLED BY A SWITCH AT THE ACCESS | | | OPENING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|