2002-06-19 00:00:00 
 ONLY ONE SET OF ENERGY CALCS SUBMITTED
 & NO MANUAL J CALCULATIONS SUBMITTED.
  
 AS PER 1997 SMC 304.4.1, ACCESS OPENING
 FOR EQUIPMENT IN THE ATTIC SHALL BE NO
 LESS THAN 22" X 36" CONTINUOUS FROM THE
 OPENING TO ITS CONTROLS.AS PER COUNTY
 WIDE AMMENDMENTS 304.4.2 EQUIPMENT IN
 THE ATTIC MUST ALSO HAVE AN ACCESSIBLE
 DISCONNECT SWITCH & A 110-120 VOLT A/C
 GROUNDING TYPE CONVENIENCE OUTLET & A
 LIGHT ON THE SERVICE SIDE OF THE EQUIP.
 CONTROLED BY A SWITCH AT THE ACCESS
 OPENING.
  