Plan Review Notes
Plan Review Notes For Permit 02021424
Permit Number 02021424
Review Stop R
Sequence Number 1
Notes
Date Text
2002-04-05 00:00:00CHECKLIST:
 1-AFTER CORRECTING ORIGINAL DRAWINGS,
 PLEASE PAY IMPACT FEES TO PALM BEACH
 COUNTY. BRING BACK STAMPED DRAWINGS
 AND PAID RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-CONTRACTOR TO UPDATE INSURANCES.
 4-UPDATE/REVISE DRAWINGS. SEE COMMENTS
 ON PLANS. PLEASE, BRING BACK REVIEWED
 SET TO EXPEDITE REVIEW PROCESS.
 5-OWES $662.35 FOR UPDATED VALUATION AND
 RADON FEES.
 6-PROVIDE EGRESS WINDOW THAT COMPLIES
 WITH SEC. 1005.4 SBC 1997 AT LIBRARY.
 OR, WRITE VISIBLE NOTE UNDER LIBRARY
 STATING THAT ROOM NOT TO BE USED FOR
 SLEEPING PURPOSES (AS PER BUILDING
 OFFICIAL INTERPRETATION).
 7-PROVIDE ATTIC ACCESS AT ENTRY CUPOLA,
 AND MASTER BEDROOM WING. SEE SECTION
 2309.6 SBC 1997.
 8-CLEARLY SPECIFY ON PLANS AREAS TO HAVE
 SAFETY GLASS. SEE PLANS AND SECTION
 2405.2 SBC 1997.
 9-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOOR. SEE SIZE & SHAPE ON PLANS.
 B)GARAGE SWING DOOR. SEE SIZE AND TYPE.
 C)FRENCH DOORS. SEE SIZES ON PLANS.
 D)CASEMENT WINDOWS (MISSING DRAWINGS)
 E)WINDOW MULLIONS(IMPACT IF USING
 IMPACT WINDOWS).
 F)FIXED WINDOWS. SEE SIZES ON PLANS.
 G)ARCHED WINDOWS. SEE SIZES ON PLANS.
 H)FIREPLACE UL LISTING & COMPLETE SPECS.
 I)EXT. DOOR @ 3RD FL. BALCONY. SEE SIZE
 AND SHAPE ON PLANS.
 10-SPECIFY HEIGHT OF CHIMNEY TO VERIFY
 COMPLIANCE WITH SEC. 2804 SBC 1997.
 11-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING INSTALLATION AT PORCHES.
 SPECIFY ALL FASTENERS AS REQUIRED. SEE
 ASTM C-1063. (SEC. 2505.2 SBC 1997)
 12-INFORMATION ON DESIGN CERTIFICATION
 BUILDING CODE COMPLIANCE FORM IS
 INCORRECT. SEE TABLE 1606.2A SBC 1997.
 NOTE: INFORMATION IN THIS FORM SHALL BE
 INCLUDED ON PLANS. NO SEPARATE FORM.
 13-PROVIDE TWO COPIES OF ENERGY CALCS.
 14-PROVIDE CURRENT SOIL TEST REPORT.
 SEE COMMENTS ON REPORT SUBMITTED.
 15-PROVIDE COMPLETE INFORMATION FOR
 SHUTTERS INCLUDING KEY PLAN & COMPLETE
 INSTALLATION SCHEDULE (SEE SAMPLE).
 ALSO, ON STORM PANEL DWGS INDICATE
 SPECIFIC MOUNTING CODITIONS AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO MEAN ROOF HEIGHT, DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 16-SPECIFY DRAINAGE AND SCUPPERS FOR
 BALCONY AT THIRD FLOOR. SEC 1503.1.2.3
 AND 1517.6.4 SBC 1997.