Plan Review Notes
Plan Review Notes For Permit 02021424
Permit Number 02021424
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-02 00:00:00DENIED;
 RISER DIAGRAM;
 1.ONLY 2 W/C PERMITED ON 3" HORIZONTAL
 BRANCH 94 SPC TABLE 714.1 NOTE 3 (4"
 REQUIRED DOWN STREAM OF RISER TO BATH
 2 AND 3.
 2.TUB IN BATH 3 UNVENTED.
 3.BATH 4 2" TRAP AND DRAIN REQUIRED PER
 TABLE 713.1
 4.MASTER BATH BIDET NOT VENTED,2" REQ.
 FOR SHOWER.
 PLUMBING NOTES: PAGE 1
 NOTE 5 SHOCK ARRESTOR SHALL BE INSTALLED
 PER MANUFACTORS RECOMMENDATIONS AND SPC
 SEC 607.8.2.
 NOTE 8 MAXIMUM FLOW FOR SHOWER HEADS IS
 2.5 GAL PER MIN TABLE 406.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369