| Plan Review Notes For Permit 02021424 |
| Permit Number |
02021424 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-02 00:00:00 | DENIED; | | | RISER DIAGRAM; | | | 1.ONLY 2 W/C PERMITED ON 3" HORIZONTAL | | | BRANCH 94 SPC TABLE 714.1 NOTE 3 (4" | | | REQUIRED DOWN STREAM OF RISER TO BATH | | | 2 AND 3. | | | 2.TUB IN BATH 3 UNVENTED. | | | 3.BATH 4 2" TRAP AND DRAIN REQUIRED PER | | | TABLE 713.1 | | | 4.MASTER BATH BIDET NOT VENTED,2" REQ. | | | FOR SHOWER. | | | PLUMBING NOTES: PAGE 1 | | | NOTE 5 SHOCK ARRESTOR SHALL BE INSTALLED | | | PER MANUFACTORS RECOMMENDATIONS AND SPC | | | SEC 607.8.2. | | | NOTE 8 MAXIMUM FLOW FOR SHOWER HEADS IS | | | 2.5 GAL PER MIN TABLE 406. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|