| 2002-04-20 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - SGC-97 - FACBC-97 |
| | |
| | 1) FROM PREVIOUS REVIEW (#2) PLEASE SHOW |
| | ON PLANS APPROVED AIR CHAMBERS, (SEE |
| | ATTACHED SHEET). AIR CHAMBERS SHALL BE |
| | RECHARGEABLE AND ACCESSIBLE PER SPC SEC |
| | 607.8.3SHT P-5.1 |
| | 2) FROM PREVIOUS REVIEW. SHT P5.1 WATER |
| | ISOMETRIC, DOUBLE LAVS AND DRINKING |
| | FOUNTAIN (3 FIXTURES) ARE BEING SUPPLIED |
| | WITH 1/2" COLD. MAXIMUM FIXTURES SUPPLI- |
| | ED WITH 1/2" COLD IS 2 FIXTURES. MODEL |
| | COUNTYWIDE AMENDMENTS TO THE SPC-94 SEC |
| | 607.7. THIS HAS NOT BEEN CHANGED. |
| | 3) FOLLOWING GAS PERMIT APPLICATION REQ- |
| | UIREMENTS HAVE NOT BEEN ADDRESSED. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER STANDARD |
| | GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER STANDARD GAS CODE SEC. 305.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | STANDARD GAS CODE SEC. 402. |
| | E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. SHOW THIS |
| | ON GAS RISER DIAGRAM |
| | F. SHT P5.1 GAS PIPING ISOMETRIC, TRENCH |
| | W/OPEN GRATE STILL SHOWN ON PLAN. INDIC- |
| | ATE ON PLAN THAT PIPE WILL BE PAINTED |
| | WITH A BITUMASTIC PAINT AND FILL TRENCH |
| | WITH A LIGHT WEIGHT CONCRETE TO ALLOW |
| | FOR EASY REMOVAL AND SERVICE OF PIPE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |