| Plan Review Notes For Permit 02021392 |
| Permit Number |
02021392 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-01 00:00:00 | ****************** UNSAT ************ | | | | | | 1)NOTE: PLEASE CLARIFY LOADS SHOWN FOR | | | SOME RECEPT CIRCUITS ARE AT 180VA PER | | | OUTLET. PLEASE NOTE SOME DO NOT SHOW | | | THE SAME AMOUNT/ PLEASE DOUBLE CHECK | | | LOADS FOR OUTLETS SHOWN. PLEASE SEE | | | 220-3/220-10/220-11/220-13 | | | LOAD WATTS PER SQ FT ETC. | | | PLEASE NOTE THAT IT HAS BEEN COMMON TO | | | SHOW CONNECTED LOADS. WE STILL NEED TO | | | SEE THE CALCS. | | | | | | 2)NOTE: PLEASE SHOW LOADS FOR TRACK | | | LIGHTING PER 220-12B. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORAMTION FOR | | | REVEIW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|