Plan Review Notes
Plan Review Notes For Permit 02021370
Permit Number 02021370
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-11 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE MEANS OF DISCONNECT
 FOR DETACHED STRUCTURE.
 225-31
  
 2)NOTE: PLEASE NOTE MEANS OF GROUNDING
 AT DETACHED BLDG. PER 250-32.
  
 3)NOTE: PLEASE NOTE MISSING OUTLET PER
 210-52 UPSTAIRS WALL. OVER 2'.
  
 4)NOTE: PLEASE NOTE MISSING OUTLET FOR
 KITCHEN PENINSULAR. 210-52C-3.
  
 5)NOTE: PLEASE NOTE MISSING BLDG/FOOTER
 STEEL PER 250-50. GROUNDING ELECTRODE
 SYSTEM.
  
 6)NOTE: PLEASE NOTE CLEARENCE FOR A/C
 COND UNIT DISCONNECTS PER 110-26.
  
 7)NOTE: PLEASE NOTETHAT RISER DIAGRAM
 SHOWS MAIN DISCONNECT NEXT TO METER
 AND FLOOR LAYOUT NEEDS TO SHOW MAIN DISC
 NEXT TO METER.
  
 8)NOTE: PLEASE NOTE CLEARENCE FOR CLOSET
 LT UNDER STAIRS(TYPE OF FIXTURE).
  
 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12. ON PANEL SCHEDULE
  
 10)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372