| Plan Review Notes For Permit 02021370 |
| Permit Number |
02021370 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-11 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE MEANS OF DISCONNECT | | | FOR DETACHED STRUCTURE. | | | 225-31 | | | | | | 2)NOTE: PLEASE NOTE MEANS OF GROUNDING | | | AT DETACHED BLDG. PER 250-32. | | | | | | 3)NOTE: PLEASE NOTE MISSING OUTLET PER | | | 210-52 UPSTAIRS WALL. OVER 2'. | | | | | | 4)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | KITCHEN PENINSULAR. 210-52C-3. | | | | | | 5)NOTE: PLEASE NOTE MISSING BLDG/FOOTER | | | STEEL PER 250-50. GROUNDING ELECTRODE | | | SYSTEM. | | | | | | 6)NOTE: PLEASE NOTE CLEARENCE FOR A/C | | | COND UNIT DISCONNECTS PER 110-26. | | | | | | 7)NOTE: PLEASE NOTETHAT RISER DIAGRAM | | | SHOWS MAIN DISCONNECT NEXT TO METER | | | AND FLOOR LAYOUT NEEDS TO SHOW MAIN DISC | | | NEXT TO METER. | | | | | | 8)NOTE: PLEASE NOTE CLEARENCE FOR CLOSET | | | LT UNDER STAIRS(TYPE OF FIXTURE). | | | | | | 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTION PER 210-12. ON PANEL SCHEDULE | | | | | | 10)NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|