| 2002-06-05 00:00:00 | BUILDING DENIED |
| | |
| | 1) THE ENERGY CALC. FORM THAT WAS |
| | SUBMITTED IS FOR ADDITIONS OF 600 SQ.FT. |
| | OR LESS. PLEASE SUBMIT (2) COPIES OF THE |
| | PROPER FORM. SEE ATTACHED. |
| | |
| | 2) PLEASE ADDRESS THE LETTER CONCERNING |
| | THE STORAGE TRAILER TO THE BUILDING |
| | OFFICIAL. THE LETTER IS REQUIRED TO BE |
| | NOTARIZED. THE STORAGE CONTAINER MUST BE |
| | PERMITTED OR REMOVED FROM THE PROPERTY. |
| | |
| | 3) THE PRODUCT APPROVALS FOR THE SINGLE |
| | HUNG WINDOWS IS REQUIRED TO BE SBCCI OR |
| | METRO-DADE. IF NOT, THEN SITE SPECIFIC |
| | ENGINEERING (PRODUCT APPROVAL) IS |
| | REQUIRED. SITE SPECIFIC ENGINEERING |
| | REQUIRES THE WET SIGNATURE, DATE AND |
| | EMBOSSED SEAL OF THE ENGINEER THAT IS |
| | CERTIFYING THE PRODUCT AND OF AN |
| | ENGINEER OR ARCHITECT APPROVING THE |
| | INSTALLATION IN THE STRUCTURE. SEE THE |
| | ATTACHED FORM. |
| | |
| | 4) EASEMENT RELEASES ARE REQUIRED FROM |
| | WPB WATER UTILITIES DEPT., TELEPHONE |
| | AND CABLE COMPANIES. SEE ATTACHED. |
| | |
| | 5) THE PERSON RESPONSIBLE FOR THE DESIGN |
| | OF THE STRUCTURE IS REQUIRED TO SIGN THE |
| | PLANS. CITY AMENDMENTS 104.2.1 |
| | |
| | 6) PROVIDE KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR STORM PANELS. INDICATE THE |
| | FASTENER TYPE THAT WILL BE USED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |