| Date |
Text |
| 2002-03-08 00:00:00 | ****************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT |
| | COMPLETE FOR PROPER REVIEW. |
| | |
| | 2)NOTE: PLEASE NOTE, LOAD CALCULATIONS |
| | ARE REQ`D FOR ADDITIONS OVER 500SQ FT. |
| | 220-3-C1 |
| | |
| | 3)NOTE: PLEASE NOTE MORETHAN 50% IS |
| | BEING DONE, SD`S WILL BE REQ`D INSIDE |
| | AND OUTSIDE EXISING BEDROOMS AND |
| | ALSO ANY OTHER ELEC THAT MAY BE NEEDED |
| | TO MEET CODE. |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | PLEASE NOTE MISSING SD OUTSIDE BEDROOMS. |
| | |
| | 6)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| | PROTECTION ON PANEL SCHEDULE PER 210-12. |
| | |
| | 7) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.2 |
| | MECHANICAL CODE. PLEASE SHOW LOCATION |
| | OF NEW EQUIPMENT ON ELEC AND DISC`S PER |
| | 440-11. |
| | |
| | 8)NOTE:PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | IT IS NOT CLEAR IF ANY NEW SERVICE IS |
| | BEING ADDED. |
| | |
| | |
| | PLEASE COMPLETE PLANS AND RE-SUBMIT FOR |
| | REVIEW. PLEASE SUBMIT ALL OF THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |