Plan Review Notes
Plan Review Notes For Permit 02021340
Permit Number 02021340
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 COMPLETE FOR PROPER REVIEW.
  
 2)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 ARE REQ`D FOR ADDITIONS OVER 500SQ FT.
 220-3-C1
  
 3)NOTE: PLEASE NOTE MORETHAN 50% IS
 BEING DONE, SD`S WILL BE REQ`D INSIDE
 AND OUTSIDE EXISING BEDROOMS AND
 ALSO ANY OTHER ELEC THAT MAY BE NEEDED
 TO MEET CODE.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE NOTE MISSING SD OUTSIDE BEDROOMS.
  
 6)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION ON PANEL SCHEDULE PER 210-12.
  
 7) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE. PLEASE SHOW LOCATION
 OF NEW EQUIPMENT ON ELEC AND DISC`S PER
 440-11.
  
 8)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 IT IS NOT CLEAR IF ANY NEW SERVICE IS
 BEING ADDED.
  
  
 PLEASE COMPLETE PLANS AND RE-SUBMIT FOR
 REVIEW. PLEASE SUBMIT ALL OF THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372