Plan Review Notes For Permit 02021177
Permit Number 02021177
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-02-20 00:00:00A) PLEASE INDICATE HOURS OF OPERATION
 AND AGES OF CHILDREN EXPECTED WITHIN
 THE EXISTING BUILDING.
 B) IS THE EXISTING BUILDING SPRINKLER
 PROTECTED OR NOT.
 C) PLEASE INDICATE WINDOWS FOR RESCUE
 ON THE PLANS. PLEASE INDICATE SIZES
 OF WINDOWS.
 D) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 E) IF NO FIRE SPRINKLERS ARE PRESENT,
 ELECTRICAL ROOM 902 IS REQUIRED TO BE
 AT LEAST ON HOUR FIRE RATED.
 F) PLEASE INDICATE LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.
 G) PANIC HARDWARE WILL BE REQUIRED ON
 EXIT DOORS BASED ON OCCUPANT LOAD
 COUNTS PROVIDED WITH PLANS.
 H) ANY CORRIDORS ARE REQUIRED TO BE
 AT LEAST 1/2 HOUR RATED.
 I) IT APPEARS THAT WINDOWS ARE LOCATED
 NEAR THE EXIT DOORS, NEAR ROOMS 202
 AND 204.
 J) PLEASE PROVIDE MORE DETAILS ON
 EXISTING STAIRS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910