| 2002-03-01 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) UNTIL MARCH 1, 2002 EITHER STANDARD |
| | BUILDING CODE 1997 OR FLORIDA BUILDING |
| | CODE 2001 MAY BE USED.NEITHER CODE IS |
| | REFERENCED ON THE PLANS.STATE WHICH |
| | CODE THE WORK IS TO BE CONSTRUCTED TO. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC 1012.1.4SECOND FLOOR EXIT DOOR |
| | 201/2.THE SWING OF THE RELOCATED DOOR |
| | OBSTRUCTS THE ROUTE TO THE STAIRS. |
| | MOVE/RECONFIGURE THE DOOR TO AVOID |
| | OBSTRUCTION OF THE MEANS OF EGRESS. |
| | |
| | 4) FBC 2405.2THE GLAZING IN DOOR 201-1 |
| | IS IN A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER |
| | PRODUCT SAFETY COMMISSION 16, CODE OF |
| | FEDERAL REGULATIONS, PART 1201 |
| | (CPSC 16-CFR, PART 1201).SUBMIT |
| | DETAILS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 5) FBC* 104.2.1.2SHEET A1.2, DETAIL 5 |
| | AND DOOR ELEVATIONS.STATE THE |
| | THICKNESS OF THE TEMPERED GLASS IN THE |
| | DOOR AND STOREFRONT.ALSO, AMEND THE |
| | FLOOR PLAN TO CLARIFY THE LOCATION OF |
| | DOOR ELEVATION D. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |