| 2002-02-25 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE CLARIFY "ER"? EXISTING | | | RELOCATE? AND "RL"? RELOCATE? | | | SHOW AS NOTE> | | | | | | 2)NOTE: PLEASE NOTE THAT 21 NEW OUTLETS | | | ARE SHOWN AS NEW ON 8TH FLOOR AND ALL | | | ARE SHOWN ON THE SAME CIRCUIT P-8? | | | PLEASE SEE 220-13 FOR LOAD PER OUTLET | | | AT 180VA. PLEASE NOTE THIS LOAD FIGURED | | | WOULD EXCEED RATING FOR CIRCUIT. PLEASE | | | ALSO NOTE THAT SAME APPLYS TO NEW | | | OUTLETS SHOWN FOR 9TH FLOOR, ALL ON THE | | | SAME CIRCUIT. PLEASE ADJUST | | | | | | 3)NOTE: PLEASE NOTE THAT FIRE COMMENTS | | | MAY CHANGE ELEC LAYOUT FOR EXITING? | | | | | | 4)NOTE: PLEASE NOTE THAT COVER SHEET | | | SHOWS "96" NEC AND WE ARE UNDER THE "99" | | | NEC. PLEASE CORRECT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|