Plan Review Notes
Plan Review Notes For Permit 02021008
Permit Number 02021008
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-25 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE CLARIFY "ER"? EXISTING
 RELOCATE? AND "RL"? RELOCATE?
 SHOW AS NOTE>
  
 2)NOTE: PLEASE NOTE THAT 21 NEW OUTLETS
 ARE SHOWN AS NEW ON 8TH FLOOR AND ALL
 ARE SHOWN ON THE SAME CIRCUIT P-8?
 PLEASE SEE 220-13 FOR LOAD PER OUTLET
 AT 180VA. PLEASE NOTE THIS LOAD FIGURED
 WOULD EXCEED RATING FOR CIRCUIT. PLEASE
 ALSO NOTE THAT SAME APPLYS TO NEW
 OUTLETS SHOWN FOR 9TH FLOOR, ALL ON THE
 SAME CIRCUIT. PLEASE ADJUST
  
 3)NOTE: PLEASE NOTE THAT FIRE COMMENTS
 MAY CHANGE ELEC LAYOUT FOR EXITING?
  
 4)NOTE: PLEASE NOTE THAT COVER SHEET
 SHOWS "96" NEC AND WE ARE UNDER THE "99"
 NEC. PLEASE CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372