| Plan Review Notes For Permit 02021008 |
| Permit Number |
02021008 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-02-26 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SBC* 104.2SHEET A8-3, 8TH FLOOR | | | REFLECTED CEILING PLAN.THE SHEET TITLE | | | STATES "NINTH FLOOR REFLECTED CEILING | | | PLAN" AND SHOULD BE CORRECTED TO READ | | | "EIGHTH FLOOR....." | | | | | | 3) SBC* 104.2SHEET A9-3, DETAIL 9.IS | | | THE 'EXISTING OPERABLE HORIZONTAL | | | ROLLING ROAD PANEL' TO BE FIXED SHUT, AS | | | IT IS CONNECTED TO THE NEW PARTITION BY | | | THE PROPOSED SEALANT AND NEOPRENE PAD | | | DETAIL?IF IT IS TO BE FIXED SHUT, IS | | | THE ADJACENT PANEL TO THE EAST AN | | | OPERABLE PANEL?ANNOTATE DETAIL 9 TO | | | CLARIFY THE PROPOSALS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|