| 2002-06-03 00:00:00 | BUILDING DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE MEAN ROOF HEIGHT GIVEN ON THE |
| | PLANS (21-5") DIFFERS FROM THE ONE |
| | GIVEN ON THE DESIGN CERTIFICATION FORM |
| | (20'-4"). PLEASE CORRECT. |
| | |
| | 3)THE ARCHITECT'S NAME AND CERTIFICATION |
| | NUMBER TYPED ON THE BOTTOM LEFT OF THE |
| | DESIGN CERTIFICATION FORM IS NOT THE |
| | ARCHITECT THAT SIGNED AND SEALED THE |
| | DOCUMENT. PLEASE CORRECT. |
| | |
| | 4) PROVIDE A SOIL BEARING TEST REPORT AS |
| | REQUIRED FOR QUESTIONABLE SOIL BEARING |
| | CAPACITY BY THE CITY OF W.P.B.AMENDMENTS |
| | TO THE 97 S.B.C. SECTION 1804.2.2. |
| | |
| | 5)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR DOUBLE OUTSWING SOLID CORE |
| | DOORS AS INDICATED ON THE PLANS FOR THE |
| | FRONT DOOR. THE ONES SUBMITTED FOR THE |
| | FRONT DOOR IS FOR A SINGLE DOOR WITH |
| | SIDELITES. |
| | |
| | 6) PROVIDE (2) COPIES OF KEY PLANS AND |
| | INSTALLATION SCHEDULES FOR STORM PANELS. |
| | INDICATE THE FASTENER TYPE THAT WILL BE |
| | USED. IF THIS INFORMATION IS NOT |
| | PROVIDED AT TIME OF PERMIT, A SEPARATE |
| | PERMIT AND ADDITIONAL FEES WILL BE |
| | REQUIRED FOR THE STORM PANELS. |
| | |
| | 7) PLEASE INSERT THE NEW PAGES INTO THE |
| | PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |