Plan Review Notes For Permit 02020988
Permit Number 02020988
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-11 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ALL CODES THAT
 ARE REFERENCED IN NOTES ARE FROM "96"
 NEC. IT HAS BEEN NOTED/REDLINED ON
 PREVIOUS PLANS FOR THE LAST YEAR OR SO.
 PLEASE MAKE CHANGES TO CODES TO REFLECT
 99' CODES. 110-26/250-122/250-140.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GRPOUNDING CONDUCTOR BETWEEN METER/MAIN
 AND PANEL. SIZE PER 250-122
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS ON PANEL SCHEDULE.210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW