| 2002-03-03 00:00:00 | PLUMBING PLAN REVIEW,FBC 2001,DENIED | | | (1) SEC 424.2.7.2 MOUNTING EQUIPMENT , | | | PROVIDE A DETAIL OF SLAB MEANS OF ANCHOR | | | ING EQUIPMENT. | | | (2) SEC 424.2.9 AUTO FILL PROVIDE DETAIL | | | LOCAL ORDINANCE #2853-95 BACK FLOW | | | PREVENTER ON WATER SERVICE. | | | (3) SEC 424.2.13.2 JOINTS,CONNECTIONS. | | | FBC 2001 PLUMBING SEC 605.21 PURPLE | | | PRIMER REQUIRED ON PVC PIPING. | | | (4) SEC 424.2.14.2 WATER RETENTION, | | | PROVIDE A DETAIL SHOWING A POSITIVE | | | MEANS OF RETANING WATER IN THE HEATER, | | | WITH BY-PASS. | | | (5) SEC 424.2.15 GAS PIPING,SEPERATE | | | PLANS AND PERMIT REQUIRED. | | | END OF COMMENTS PAUL SCHMITZ | | | 561-659-8096X8233 |
|