Plan Review Notes
Plan Review Notes For Permit 02020859
Permit Number 02020859
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-25 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE CLARIFY LOAD FOR TWO NEW
 UNITS? PLEAS NOTE, PLANS SHOW A 3P-30A
 AND NOW THATS FEDDING A 3P15 AND 3P20?
  
 2)NOTE: PLEASE ALSO CLARIFY CONDCUTORS
 SHOWN FROM AHU-12C AND CU-12C, PLEASE
 NOTE THAT PLANS SHOW ONLY ONE #12 AND
 ONE #12 GRND? DISC`S ARE SHOWN AS 3P?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372