| Notes |
| Date |
Text |
| 2002-02-25 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | 1) SPECIFY THE MAXIMUM ALLOWABLE WEIGHT | | | OF CONDENSING UNIT CU-12C, SUPPORTED BY | | | THE CANTILEVER BRACKET, ON DETAIL A02/7 | | | | | | 2) NEW DUCTWORK PENETRATION THROUGH ROOF | | | SLAB.SUBMIT DETAILS TO DESCRIBE THE | | | SIZE OF HOLE REQUIRED FOR THE NEW DUCT, | | | SLAB THICKNESS AND SPAN DIRECTION, AND | | | THE MEANS OF EDGE SUPPORT AROUND THE | | | NEW HOLES.THE ROOF PLAN (SHEET A01) | | | STATES THAT THIS DETAIL WILL BE SIMILAR | | | TO DETAIL A02/4 BUT THAT IS FOR A 5" MAX | | | DIAMETER CORE DRILLED HOLE WHICH IS MUCH | | | SMALLER. |
|