2002-02-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 1) SPECIFY THE MAXIMUM ALLOWABLE WEIGHT
 OF CONDENSING UNIT CU-12C, SUPPORTED BY
 THE CANTILEVER BRACKET, ON DETAIL A02/7
  
 2) NEW DUCTWORK PENETRATION THROUGH ROOF
 SLAB.SUBMIT DETAILS TO DESCRIBE THE
 SIZE OF HOLE REQUIRED FOR THE NEW DUCT,
 SLAB THICKNESS AND SPAN DIRECTION, AND
 THE MEANS OF EDGE SUPPORT AROUND THE
 NEW HOLES.THE ROOF PLAN (SHEET A01)
 STATES THAT THIS DETAIL WILL BE SIMILAR
 TO DETAIL A02/4 BUT THAT IS FOR A 5" MAX
 DIAMETER CORE DRILLED HOLE WHICH IS MUCH
 SMALLER.