| 2002-03-07 00:00:00 | PERMIT 02020845 |
| | ADDRESS: 425 17TH ST |
| | COMPLETE PROPRTY MANAGEMENT |
| | TEL: (561) 626-2778 |
| | |
| | |
| | 1)- PLANS DO NOT IDENTIFY AS TO WHICH |
| | CODE THE PLANS WERE DESIGNED TOO? |
| | 1997 SBC OR 2001 FLORIDA CODE? |
| | 1997 SBC OR 2001 FLORIDA CODE? |
| | 2)- THE PLANS LOOK LIKE THIS IS A 8 UNIT |
| | APT. COMPLEX, THE PLAN DOES NOT INDICATE |
| | BATHROOMS IN EACH UNIT. |
| | PLANS ARE TO BE DRAWN TO A DRAFTSMAN |
| | QUALITY WITH A MINIMUM OF 1/8" SCALE. |
| | 3)- PLANS DO NOT INDICATE THE BUCK |
| | ATACHMENT FOR WINDOWS OR DOOR. |
| | 4)- EXTERIOR ENTRY DOORS TO BE RATED |
| | AS A 20 MIN. DOOR. |
| | 5)-SBC1005.4.4. EMERGENCY ESCAPE & RES- |
| | CUE OPENINGS (WINDOWS) GIVE THE CLEAR |
| | OPEN AREA FIRST & SECOND FLOOR. |
| | 6)- FL ENERGY CODE 101.4.1 PREVIOSLY |
| | UNCONDITIONED EXISTING BUILDINGS WHICH |
| | WERE PERMITTED PRIOR TO MARCH 15, 1979 |
| | TO WHICH HEATING OR COOLING SYSTEMS ARE |
| | ADDED SHALL MEET THE PRESCRIPTIVE |
| | REQUIREMENTS OF METHOD "C" FORM 600C-97 |
| | IF DESIGNED UNDER 97 SBC OR FORM 600C-01 |
| | IF DESIGNED UNDER THE 2001 FLORIDA CODE. |
| | A FORM SHALL BE REQUIRED FOR THE WORST |
| | CASE FIRST FLOOR & SECOND FLOOR. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |