Plan Review Notes
Plan Review Notes For Permit 02020838
Permit Number 02020838
Review Stop E
Sequence Number 3
Notes
Date Text
2002-06-03 00:00:00UNSAT!
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION, MAKE ANY NECESSARY CHANGES
 TO THE DRAWINGS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE INDICATE THE AMPERE RATING OF
 THE MAIN DISCONNECT AND METER ENCLOSURE.
  
 2} NOTE THE CONDUCTOR SIZE FROM THE
 DISCONNECT TO THE PANELS,AND CLARIFY.
  
 3} THERE IS NO EQUIPMENT GROUND
 INDICATED IN ANY OF THE CONDUITS ON THE
 RISER DIAGRAM, NOR IS THE TYPE OF
 CONDUIT INDICATED.
  
 4} PANEL "B" IS SHOWN AS MLO. THE GARAGE
 REQUIRES A DISCONNECT PER 225-31 & 32,
 AND BE GROUNDED PER 250-32.
  
 5} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.CIRCUIT "A9" IS
 THE WRONG WIRE AND BREAKER SIZE TO
 COMPLYAND HAS OTHER RCEPTACLES OUTSIDE
 THE BATH.
  
 6} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 7} KITCHEN CIRCUITS MUST COMPLY WITH
 210-52(B).NOTE RECEPTACLE AND
 REFRIGERATOR ON CIRCUIT "A14" DO NOT
 COMPLY.
  
 8} BATH CIRCUIT IN THE GARAGE MUST
 COMPLY WITH 210-11(C)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8092