| 2002-06-03 00:00:00 | UNSAT! |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION, MAKE ANY NECESSARY CHANGES |
| | TO THE DRAWINGS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE INDICATE THE AMPERE RATING OF |
| | THE MAIN DISCONNECT AND METER ENCLOSURE. |
| | |
| | 2} NOTE THE CONDUCTOR SIZE FROM THE |
| | DISCONNECT TO THE PANELS,AND CLARIFY. |
| | |
| | 3} THERE IS NO EQUIPMENT GROUND |
| | INDICATED IN ANY OF THE CONDUITS ON THE |
| | RISER DIAGRAM, NOR IS THE TYPE OF |
| | CONDUIT INDICATED. |
| | |
| | 4} PANEL "B" IS SHOWN AS MLO. THE GARAGE |
| | REQUIRES A DISCONNECT PER 225-31 & 32, |
| | AND BE GROUNDED PER 250-32. |
| | |
| | 5} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG.CIRCUIT "A9" IS |
| | THE WRONG WIRE AND BREAKER SIZE TO |
| | COMPLYAND HAS OTHER RCEPTACLES OUTSIDE |
| | THE BATH. |
| | |
| | 6} PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PER 210-12 |
| | |
| | 7} KITCHEN CIRCUITS MUST COMPLY WITH |
| | 210-52(B).NOTE RECEPTACLE AND |
| | REFRIGERATOR ON CIRCUIT "A14" DO NOT |
| | COMPLY. |
| | |
| | 8} BATH CIRCUIT IN THE GARAGE MUST |
| | COMPLY WITH 210-11(C)(3). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/659-8096 EXT. 8092 |