Plan Review Notes
Plan Review Notes For Permit 02020838
Permit Number 02020838
Review Stop E
Sequence Number 2
Notes
Date Text
2002-04-10 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE THAT THERE IS NO
 ELECTRICALSHOWN FOR INSIDE OF MAIN
 HOUSE.?
  
 3))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5 )NOTE: PLEASE NOTE, EITHERMISSING
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
  
 6) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 7) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 8) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 9)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 10)NOTE:PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 11)NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
  
 12)NOTE: PLEASE NOTE THAT DISCONNECTING
 MEANS SHALL BE PROVIDEDFOR ALL
 UNGROUNDED CONDUCTORS THAT SUPPLY OR
 PASS THROUGH A BLDG/STRUCTURE.
 PER 225-31. PLEASE ALSO NOTE GROUNDING
 PER 250-50/250-32
  
 13)NOTE: PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 14)NOTE: PLEASE NOTE THAT THERE ARE NO
 CONDUCTOR SIZES SHOWN FOR SERVICE?
 NOTHING SHOWN FROM MAIN PANEL TO GARAGE
  
 15)NOTE: PLEASE CLARIFY GARAGE BEING
 SHOWN AS LIVING AREA BEING CLOSED IN
 AND NEW DRYWALL. PLEASE NOTE REQ`D ELEC.
  
 PLEASE NOTE THAT THESE COMMENTS ARE FOR
 USE AS RESIDENCE. PLEASE NOTE THAT
 THERE WOULD BE SOME OTHER NOTES FOR
 COMMERCIAL USE.
 PLEASE ALSO NOTE, SHOW REQ`D ITEMS ABOVE
 AS "EXISTING" IF INDEED THE CASE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372