| 2002-04-10 00:00:00 | ************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2)NOTE: PLEASE NOTE THAT THERE IS NO |
| | ELECTRICALSHOWN FOR INSIDE OF MAIN |
| | HOUSE.? |
| | |
| | 3))NOTE: PLEASE LIST THE REQ`D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PER 210-12 |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 5 )NOTE: PLEASE NOTE, EITHERMISSING |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | |
| | 6) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 7) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. |
| | INCLUDES KITCHEN ISLANDS. |
| | |
| | 8) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | |
| | 9)) NOTE: PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210-52E |
| | |
| | 10)NOTE:PLEASE NOTE MISSING OUTLET FOR |
| | A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| | 306 OF THE MECHANICAL CODE. |
| | |
| | 11)NOTE: PLEASE CLARIFY EQUIPMENT |
| | GROUNDING METHOD BETWEEN FIRST MEANS |
| | OF DISCONNECT AND PANELS. PLEASE SIZE |
| | CONDUCTORS PER 250-122. |
| | |
| | |
| | 12)NOTE: PLEASE NOTE THAT DISCONNECTING |
| | MEANS SHALL BE PROVIDEDFOR ALL |
| | UNGROUNDED CONDUCTORS THAT SUPPLY OR |
| | PASS THROUGH A BLDG/STRUCTURE. |
| | PER 225-31. PLEASE ALSO NOTE GROUNDING |
| | PER 250-50/250-32 |
| | |
| | 13)NOTE: PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5. |
| | |
| | 14)NOTE: PLEASE NOTE THAT THERE ARE NO |
| | CONDUCTOR SIZES SHOWN FOR SERVICE? |
| | NOTHING SHOWN FROM MAIN PANEL TO GARAGE |
| | |
| | 15)NOTE: PLEASE CLARIFY GARAGE BEING |
| | SHOWN AS LIVING AREA BEING CLOSED IN |
| | AND NEW DRYWALL. PLEASE NOTE REQ`D ELEC. |
| | |
| | PLEASE NOTE THAT THESE COMMENTS ARE FOR |
| | USE AS RESIDENCE. PLEASE NOTE THAT |
| | THERE WOULD BE SOME OTHER NOTES FOR |
| | COMMERCIAL USE. |
| | PLEASE ALSO NOTE, SHOW REQ`D ITEMS ABOVE |
| | AS "EXISTING" IF INDEED THE CASE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |