| 2002-04-22 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 02020838 |
| | 521 15TH ST |
| | CONT: STUART LEDIS, LLC |
| | TEL: 718-7162 |
| | |
| | 1)- NOTE #1 REFERRED TO WHICH CODE WAS |
| | YO BE USED, THE 1997 STANDARD BUILDING |
| | CODE USES ASCE 7/95 NOT 7/93/1994. |
| | |
| | 2)- SBC 104.2.2 ADDITIONAL INFORMATION |
| | REQUIRED, THE CITY SHALL REQUIRE A |
| | NOTIRIZED LETTER FROM THE OWNERS AS TO |
| | WHAT THE USE THESE STRUCTURES WILL BE |
| | USED FOR? |
| | THE HANDICAPPED RAMP TENDS TO LEAD |
| | US TO BELEIVE THAT THERE IS A CHANGE OF |
| | USE. IF SO, THE CONTRACTOR SHALL SUBMIT |
| | THE PLANS TO P B COUNTY FOR ASSESSMENT |
| | OF IMPACT FEES. |
| | |
| | 3)- SBC 3401.2.2.2: CHANGES IN OCCUPANCY |
| | OF A BUILDING NOW EXISTING OR HEREAFTER |
| | ERECTED SHALL NOT BE MADE UNTIL REVISED |
| | CERTIFICATE OF OCCUPANCY HAS BEEN ISSUED |
| | THE DESIGNER OF RECORD SHALL CERTIFY |
| | THAT THE EXISTING FLOOR STRUCTURE IS |
| | SUITABLE FOR THE FLOOR LOADS CHARACTERIS |
| | TIC OF THE PROPOSED OCCUPANCY. |
| | PLANS SHALL BE REQUIRED TO BE SUBMIT- |
| | TED TO P B COUNTY FOR CHANGE OF OCCUPAN- |
| | CY FOR GARAGE. |
| | |
| | 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | THE SINGLE HUNG WINDOW REPORT SUBMITTED |
| | MAY USE IMPACT OR NON IMPACT GLAZING, |
| | INDICATE WHICH IS TO BE USED. IF NON-IM |
| | PACT GLAZING IS USED THEN STORM SHUTTERS |
| | WITH LARGE MISSLE IMPACT TESTING SHALL |
| | BE REQUIRED, SBCCI OR DADE COUNTY REPORT |
| | A KEY LAYOUT PLAN AND ANCHORING SCHEDULE |
| | SHALL ACCOMPANY THE REPORT |
| | |
| | 5)- THE PLANS ALSO INDICATE 2 PAIR OF |
| | WINDOWS SHALL BE INSTALLED, PROVIDE THE |
| | MULLION REPORT FOR THIS APPLICATION. |
| | |
| | 6)- MISSING REPORT FOR AWNING TYPE |
| | WINDOWS, (OLD GARAGE STRUCTURE) |
| | |
| | 7)- GARAGE DOOR INDICATES NOT A FRENCH |
| | DOOR, SUBMIT THE CORRECT REPORT. |
| | |
| | 8)- THE HANDICAPPED RAMP, SEE FL ACCESS- |
| | IBILITY 4.8.3 CLEAR WIDTH FOR A REQUIRED |
| | MEANS OF EGRESS. |
| | 4.8.4(2) BOTTOM LANDING 72". |
| | 4.8.4(3) MINIMUM TURNING DIA. 60". |
| | |
| | 9)- PROVIDE PRODUCT TESTING FOR NEW |
| | ROOF PERMIT. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |