| 2002-04-15 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 3/7/02: |
| | |
| | 3) FBC 424.2.17.1BARRIER TO SWIMMING |
| | POOL.THIS COMMENT HAS NOT BEEN |
| | PROPERLY ADDRESSED.THE 'REVISIONS' |
| | COLUMN ON SHEET A1.00 REFERS TO THE |
| | PROVISION OF A 36" HIGH BARRIER.THE |
| | TOP OF THE BARRIERS TO SWIMMING POOLS |
| | SHALL BE AT LEAST 48" ABOVE GRADE |
| | (FBC 424.2.17.1.1).THE NEW ACCESS |
| | GATES SHALL BE IN ACCORDANCE WITH |
| | FBC 424.2.17.1.8.THE WALLS, AND |
| | ASSOCIATED DOORS/WINDOWS, THAT FORM PART |
| | OF THE BARRIER SHALL BE IN ACCORDANCE |
| | WITH FBC 424.2.17.1.9.AMEND/ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 7) SBC* 1606.4.2PRODUCT APPROVALS. |
| | THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | SUBMIT A PRODUCT APPROVAL NOTICE OF |
| | ACCEPTANCE FOR EACH OF THE NEW WINDOWS |
| | AND EXTERNAL DOORS (INCLUDING DOOR D108) |
| | |
| | 8) SBC* 1606.4.2PRODUCT APPROVALS FOR |
| | 'CUSTOM DOORS AND WINDOWS'.THIS |
| | COMMENT HAS NOT BEEN PROPERLY ADDRESSED. |
| | THE PRODUCT APPROVAL SUBMITTAL FORMS |
| | COMPLETED BY FRANK L BENNARDO, P.E. MUST |
| | BE SIGNED BY THE ENGINEER OF RECORD FOR |
| | THE PROJECT. |
| | |
| | 11) SBC* 2308EXTERIOR STUD WALL.THIS |
| | COMMENT HAS NOT BEEN PROPERLY ADDRESSED. |
| | THE PARTITION LEGEND ON SHEET A2.10 |
| | STILL REFERS TO 1/2" PLYWOOD SHEATHING |
| | FOR THE EXTERIOR STUD WALL.THE PLYWOOD |
| | SHEATHING SHALL BE MINIMUM 5/8" AS PER |
| | THE NOTE 8 ADDED TO SHEET A4.00.ALSO, |
| | DETAIL 8/A4.00 SHALL BE AMENDED (OR A |
| | DETAIL ADDED TO THE STRUCTURAL |
| | ENGINEER'S SHEETS) TO SHOW THE |
| | ATTACHMENT OF THE NEW STUD WALL TO THE |
| | EXISTING WALL, THE WORST CASE BEING IF |
| | THE POINT OF ABUTMENT DOES NOT COINCIDE |
| | WITH AN EXISTING STUD LOCATION. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |