Plan Review Notes
Plan Review Notes For Permit 02020812
Permit Number 02020812
Review Stop E
Sequence Number 4
Notes
Date Text
2002-07-01 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES ATTACHED FROM
 THE FIRST THREE REVIEWS.
  
  
  
  
 2)NOTE: PLEASE CLARIFY A/C LOAD?
 A/C AS 6.9? PLEASE NOTE LOAD SHOWN AS 15
 KW ON MECH PLANS?
 PLEASE NOTE LOAD CALCS SHOW AS 16.8KW?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE ALSO NOTE THAT E-3 STILLS
 SHOWS A/C EQUIPMENT COMING FROM OTHER
 SERVICE? SEE LOWER RIGHT HAND CORNER.
  
 4)NOTE: PLEASE SEE SHEET ATTACHED FOR
 FS/FAC 553.80(2)(B).
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE ALSO NOTE WATER HEATER LOAD SHOWN
 AS 6.0 ON LOAD CALCS AND 1.5 ON PANEL
 SCHEDULE?