| Plan Review Notes For Permit 02020812 |
| Permit Number |
02020812 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-07-01 00:00:00 | ************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE NOTES ATTACHED FROM | | | THE FIRST THREE REVIEWS. | | | | | | | | | | | | | | | 2)NOTE: PLEASE CLARIFY A/C LOAD? | | | A/C AS 6.9? PLEASE NOTE LOAD SHOWN AS 15 | | | KW ON MECH PLANS? | | | PLEASE NOTE LOAD CALCS SHOW AS 16.8KW? | | | PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE ALSO NOTE THAT E-3 STILLS | | | SHOWS A/C EQUIPMENT COMING FROM OTHER | | | SERVICE? SEE LOWER RIGHT HAND CORNER. | | | | | | 4)NOTE: PLEASE SEE SHEET ATTACHED FOR | | | FS/FAC 553.80(2)(B). | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | PLEASE ALSO NOTE WATER HEATER LOAD SHOWN | | | AS 6.0 ON LOAD CALCS AND 1.5 ON PANEL | | | SCHEDULE? |
|