| 2002-06-04 00:00:00 | ****************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT RESPONSE |
| | LETTER NOTES COMPLIANCE WITH GROUPING OF |
| | MAINS AND SUPPLYING A/C EQUIPMENT FROM |
| | PANEL "A", HOWEVER ONLY SHEET E-2 HAS |
| | BEEN CHANGED TO REFLECT THOSE CHANGES. |
| | PLEASE NOTE THAT E-3 STILL SHOWS OLD |
| | CONFIGURATION . |
| | |
| | 2)NOTE: PLEASE REVISE PANEL SCHEDULE |
| | AND LOAD CALCULATIONS TO CORRELATE WITH |
| | E-2. |
| | |
| | ***NOTE** |
| | PLEASE DO NOT SUBMIT "EXTRA" REVISED |
| | SHEETS. PLEASE TAKE OLD SHEETS OUT AND |
| | INSERT NEW/REVISED SHEETS FOR TWO |
| | COMPLETE SETS FOR REVIEW. |
| | |
| | ***** NOTE****** |
| | PLEASE ALSO NOTE THAT THERE MAY BE SOME |
| | CHANGES NEEDED FOR OTHER TRADES DUE TO |
| | THE PLANS NEEDING TO MEET 2001 FBC. |
| | PLEASE NOTE THAT PLANS WERE NEVER |
| | SUBMITTED FOR PERMIT, ONLY "PLAN REVIEW" |
| | PLEASE ALSO NOTE THAT WE ARE STILL UNDER |
| | THE "99" NEC AND ONLY CHANGES TO FIRE/ |
| | OR MECH MAY CHANGE E-SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION AS |
| | SET FORTH IN NOTE(1) WHEN ALL REVIEWS |
| | ARE DONE. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |