| 2002-06-11 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | NOTE: |
| | THE PLANS WERE ORIGINALLY SUBMITTED FOR |
| | PLAN REVIEW UNDER 1997 STANDARD BUILDING |
| | CODE PRIOR TO MARCH 1, 2002.CHANGE OF |
| | STATUS FROM PLAN REVIEW TO PERMIT |
| | APPLICATION AFTER THAT DATE REQUIRES |
| | THAT THE PLANS BE REVIEWED FOR |
| | COMPLIANCE WITH 2001 FLORIDA BUILDING |
| | CODE.THIS REVIEW HAS BEEN CARRIED OUT |
| | TO THE NEW CODE.THE PLANS SHALL NOT |
| | MAKE REFERENCE TO THE OUTGOING CODE. |
| | |
| | SHEET CS, COVER SHEET, SHALL BE AMENDED |
| | TO REFER TO 2001 FLORIDA BUILDING CODE |
| | INSTEAD OF 1997 SATNDARD BUILDING CODE. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 4/19/02: |
| | |
| | 3) FBC 1606.1.4PROTECTION OF OPENINGS |
| | PLEASE NOTE THAT THE STOREFRONT DOOR |
| | PRODUCT APPROVAL NOTICE OF ACCEPTANCE |
| | NO. 01-0919.02, SHEET 2, SPECIFIC |
| | CONDITIONS, ITEM 3.2 STATES THAT THE |
| | DOOR UNIT SHALL ONLY BE INSTALLED AT |
| | LOCATIONS PROTECTED BY A CANOPY OR |
| | OVERHANG.REFER TO THE PRODUCT APPROVAL |
| | FOR FURTHER DETAILS AND DESCRIBE THE |
| | METHOD PROPOSED TO RESTRICT WATER |
| | INFILTRATION. |
| | |
| | 6) FBC 11-4.1.3(10)ACCESSIBLE DRINKING |
| | FOUNTAIN.BOTH DETAIL 6/A-5 AND 20/A-5 |
| | SHOW THE 36" MAXIMUM HEIGHT DIMENSION |
| | INCORRECTLY.THE DIMENSION SHOULD SHOW |
| | 36" MAXIMUM SPOUT HEIGHT ABOVE THE FLOOR |
| | SEE FIG. 27. |
| | |
| | THE FOLLOWING COMMENT IS A RESULT OF THE |
| | REVISIONS TO THE PLANS SINCE THE LAST |
| | REVIEW: |
| | |
| | C) FBC 704.1OCCUPANCY SEPARATION. |
| | SHEET A-1, PARTITION TYPE A2 IS REQUIRED |
| | TO BE TWO-HOUR FIRE-RATED.AMEND THE |
| | PLANS TO SHOW THE UL LISTING REFERENCE |
| | FOR THE PROPOSED TWO-HOUR ASSEMBLY. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |