| Plan Review Notes For Permit 02020812 |
| Permit Number |
02020812 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-04-24 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CLARIFY IF SECOND SERVICE | | | IS PERMITTED DUE TO DIFFERENT VOLTAGES, | | | (230-2), PLEASE NOTE GROUPING OF MAINS | | | PER 230-72. PLEASE NOTE LIFE SAFETY | | | ISSUE IF FIRE DEPT SHUTS DOWN MAIN FOR | | | ELECTRICAL IN UNIT AND THEN 277/480V | | | IS STILL PRESENT. PLEASE NOTE THAT THIS | | | CREATES A PROBLEM. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|