Plan Review Notes
Plan Review Notes For Permit 02020812
Permit Number 02020812
Review Stop E
Sequence Number 2
Notes
Date Text
2002-04-24 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY IF SECOND SERVICE
 IS PERMITTED DUE TO DIFFERENT VOLTAGES,
 (230-2), PLEASE NOTE GROUPING OF MAINS
 PER 230-72. PLEASE NOTE LIFE SAFETY
 ISSUE IF FIRE DEPT SHUTS DOWN MAIN FOR
 ELECTRICAL IN UNIT AND THEN 277/480V
 IS STILL PRESENT. PLEASE NOTE THAT THIS
 CREATES A PROBLEM.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372