| Date |
Text |
| 2002-04-19 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 2/25/02: |
| | |
| | 3) SBC 1606.4PROTECTION OF OPENINGS. |
| | THE DETAIL 4/A-3 REFERENCE TO PRODUCT |
| | APPROVALS FOR THE STOREFRONT IS NOTED. |
| | HOWEVER, TWO COPIES OF EACH PRODUCT |
| | APPROVAL NOTICE OF ACCEPTANCE, WITH |
| | ASSOCIATED APPROVED DRAWINGS, MUST BE |
| | SUBMITTED. |
| | |
| | 6) FL ACC CODE 4.1.3(10)ACCESSIBLE |
| | DRINKING FOUNTAIN.ON DETAIL 6/A-5, |
| | BREAKROOM/KITCHEN ELEVATION, THE 27" |
| | MINIMUM LEG CLEARANCE HEIGHT DIMENSION |
| | IS SHOWN INCORRECTLY.ADD A SIDE |
| | ELEVATION OF THE DRINKING FOUNTAIN TO |
| | DEMONSTRATE COMPLIANCE WITH THIS, AND |
| | EACH OF THE OTHER, CLEARANCE/REACH |
| | REQUIREMENTS SHOWN IN FIG. 27 |
| | |
| | |
| | THE FOLLOWING COMMENTS RESULT FROM THE |
| | REVISIONS TO THE PLANS SINCE THE LAST |
| | REVIEW: |
| | |
| | A) FL ACC CODE FIG. 30(A)TOILET STALLS |
| | THE REVISION OF THE TOILET LAYOUT IS |
| | NOTED.TOILET 1 SHALL HAVE ACCESSIBLE |
| | STALL DIMENSIONS OF 60"WIDE AND 59"DEEP |
| | FOR A FLOOR MOUNTED W.C.IF THE W.C. |
| | WERE CHANGED TO WALL MOUNTED, THEN THE |
| | MIN. STALL DIMENSIONS SHALL BE 60"WIDE |
| | AND 56"DEEP.ANNOTATE/AMEND THE PLANS |
| | TO DEMONSTRATE COMPLIANCE. |
| | |
| | B) SBC* 104.2.3THE REVISED |
| | ARCHITECTURAL PLANS ARE NOT PROPERLY |
| | SEALED. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |